7.6 Set Up Thermocouple Page

-----
SET UP T/C
-----
T/C Type
700
Preset Temp
SET UP OUTPUTS
Set Up Thermocouple
Page header
Thermocouple Type
Set the thermocouple type required: Type K, R, S or NONE. If thermocouple
type is set to NONE, a preset temperature must be used – see below.
NONE
K
R
S
Preset Temperature
If a thermocouple is not used, set the process temperature.
[600 to 1400°C in 1°C steps]
Note. This frame is not displayed unless
NONE.
Press
Press
to return to the top of the
Oxygen Calibration Page.
to advance to the
Set Up Outputs Page.
7 PROGRAMMING...
is set to
Thermocouple Type
19