Set Up Input (Process Variable, Remote Set Point And Position Feedback); Set Up Input; Input Types - ABB COMMANDER 1900 Series Programming Manual

Circular chart recorders
Hide thumbs Also See for COMMANDER 1900 Series:
Table of Contents

Advertisement

...3.1 Set Up Input

SEt UP
INPUt
SELECt
PV–4
PV–3
PFb–2
rSP–2
PV–2
PFb–1
rSP–1
PV–1
NONE
INtYP
rtd
tCPL
VOLt
LO OHM
HI OHM
MAMP
MVLt
NONE
NONE
LNtYP
5/2
3/2
SQrt
rtd
tC–b
tC–N
tC–E
tC–J
tC–t
tC–S
tC–r
tC–K
NONE
Page Header – Set Up Input (Process Variable)
To advance to
Set Up Pen Range Page
Select Channel
Select the channel to be programmed:
PV–4
process variable on channel 4
PV–3
process variable on channel 3
PFb–2
valve position feedback on controller 2
rSP–2
remote set point on controller 2
PV–2
process variable on channel 2
PFb–1
valve position feedback on controller 1
rSP–1
remote set point on controller 1
PV–1
process variable on channel 1
NONE
None
Note. In the remaining frames press the
Input Type (Process Variable)
Caution. Ensure the correct input link positions are selected and the input is wired
correctly – see Section 6,
CONNECTIONS & LINKS
Select the input type required:
rtd
Resistance thermometer
tCPL
Thermocouple
VOLt
Voltage
LO OHM
Low resistance (≤750Ω)
HI OHM
High resistance (>750Ω)
MAMP
Current
MU. L t
Millivolt (≤150mV)
NONE
None
Linearizer Type
Select the linearizer type required:
5/2
x
5/2
Open channel flow applications
3/2
x
3/2
SQrt
Square Root
rtd
Resistance thermometer
tC–b
Type B thermocouple
tC–N
Type N thermocouple
tC–E
Type E thermocouple
tC–J
Type J thermocouple
tC–t
Type T thermocouple
tC–S
Type S thermocouple
tC–r
Type R thermocouple
tC–K
Type K thermocouple
NONE
No linearizer
Continued on next page.
3 BASIC CONFIGURATION LEVEL...
press the
switch.
only displayed if selected in the
Input Asignment Page
only displayed if selected in the
Input Asignment Page
switch to view the channel selected.
.
Not available on position feedback input