2.3 Connection Diagram
The following diagram shows the connection between the
GOT and the microcomputer.
2.3.1
RS-232 cable
Connection diagram
(1) RS-232 connection diagram 1)
Example of the case where the DTR/DSR signal is not used
GOT side
CD
1
RD(RXD)
2
SD(TXD)
3
ER(DTR)
4
SG
5
DR(DSR)
6
RS(RTS)
7
CS(CTS)
8
-
9
Example of the case where the DTR/DSR signal is used
GOT side
CD
1
RD(RXD)
2
SD(TXD)
3
ER(DTR)
4
SG
5
DR(DSR)
6
RS(RTS)
7
CS(CTS)
8
-
9
Precautions when preparing a cable
(2) Cable length
The length of the RS-232 cable must be 15m or less.
(3) GOT side connector
For the GOT side connector, refer to the following.
1.4.1 GOT connector specifications
(1) RS-422 connection diagram 1)
Host side
FG
SD(TXD)
RD(RXD)
RS(RTS)
SG
CS(CTS)
-
-
POINT
POINT
POINT
ER(DTR)
Host side
FG
SD(TXD)
RD(RXD)
(2) Cable length
DR(DSR)
SG
ER(DTR)
RS(RTS)
CS(CTS)
(3) GOT side connector
5V
(1) GOT side
2. MICROCOMPUTER CONNECTION (SERIAL)
2.3.2
RS-422 cable
Connection diagram
GOT side
RDA
2
RDB
7
SDA
1
SDB
6
RSA
3
RSB
8
CSA
4
CSB
9
SG
5
The polarity A and B in signal names may be reversed
depending on the microcomputer to be used.
Prepare a cable according to the microcomputer to be
used.
Precautions when preparing a cable
The distance between the GOT and the PLC of
connection diagram 1), 2) and 3) must be 1200 m or
less.
The length of the RS-422 connection diagram 4) or RS-
422 connection diagram 5) must be 30m or less.
For the GOT side connector, refer to the following.
1.4.1 GOT connector specifications
Connecting terminating resistors
Set the terminating resistor setting switch of the GOT
main unit to "Disable".
For the procedure to set the terminating resistor, refer
to the following.
1.4.3 Terminating resistors of GOT
2.3 Connection Diagram
2
Host side
SDA
SDB
RDA
RDB
-
-
-
-
SHELL