Table 10. Electrical input connections
Model
55594-8PX, 5594-8KX
5594-9PX, 5594-9KX
Table 11. Electrical output
All models
Normal mode
Voltage regulation
±1%
Efficiency
> 98% (High Efficiency mode)
> 94.5% for 8-11kVA models
Frequency
Sync with line ±5% of nominal line
regulation
frequency (outside this range: ±0.5% of
auto-selected nominal frequency)
Frequency
50 or 60Hz, autosensing or configurable as a frequency converter
Output overload
100-102% : no alarm
102-110% : load transfers to Bypass mode after 2 minutes
110-125% : load transfers to Bypass mode after 1 minute
125-150% : load transfers to Bypass mode after 10s
> 150% : load transfers to Bypass mode after 900ms
Output overload
100-125% : no alarm
(Bypass mode)
125-150% : UPS shuts down after 1 minute
> 150% : UPS shuts down after 1s
Voltage waveform
Sinewave
Harmonic
< 2% THDV on linear load
distortion
< 5% THDV on non-linear load
Transfer time
Online mode: 0 ms (no break)
High Efficiency mode: 10ms maximum (due to loss of utility power)
Power factor
0.9
Load crest ratio
3 to 1
Table 12. Electrical output connections
Model
5594-8PX, 5594-8KX
5594-9PX, 5594-9KX
Input connection
Hardwired
Output connection
(4) C19 via MBP
Input cable
Not provided
Battery mode
±1%
> 91%
±0.5% of auto-selected
nominal frequency
Output cable
Not provided