3. Insert a power cable (refer to Table 2 on page 26 for cable cross-section)
through the cable gland of the MBP Bypass Input cover
provided in the packaging).
4. Connect the wires to the Input BP terminal blocks of the MBP Bypass Input
cover
.
5. Tighten the cable gland.
6. Slide back and secure the MBP Bypass Input cover
7. Connect the two integrated power cables
Bypass Input power cable to the UPS I/O terminal blocks, following color
coding on the cables and the UPS I/O cover: blue for UPS Input; red for UPS
Output; yellow for UPS Input Bypass. Remove the Input Bypass AC jumper
on UPS.
8. Connect the MBP detection cable
9. Slide the MBP I/O cover after removing the 5 screws, to access to MBP
terminal blocks.
. (The cable is not
with the 3 screws.
and the previously installed
to the specific UPS connector.