03/2009
Remedy:
- check the motor data.
- check the motor circuit configuration (star-delta).
- check the motor load.
- check the power cable connections.
- check the power cables for short-circuit or ground fault.
- check the length of the power cables.
230033
<location>Power unit: Hardware current limiting, phase W
Message
-
value:
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
Hardware current limit for phase W responded. The pulsing in this phase is inhibited for one pulse
period.
- closed-loop control is incorrectly parameterized.
- fault in the motor or in the power cables.
- the power cables exceed the maximum permissible length.
- motor load too high
- power unit defective.
Note:
Alarm A30031 is always output if the hardware current limit for phase U, V or W on a Power Module
responds.
Remedy:
- check the motor data.
- check the motor circuit configuration (star-delta).
- check the motor load.
- check the power cable connections.
- check the power cables for short-circuit or ground fault.
- check the length of the power cables.
230035
<location>Power unit: Air intake overtemperature
Message
%1
value:
Drive object:
All objects
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
The air intake in the power unit has exceeded the permissible temperature limit.
For air-cooled power units, the temperature limit is at 55 °C.
- ambient temperature too high.
- insufficient cooling, fan failure.
Fault value (r0949, interpret decimal):
Temperature [1 bit = 0.01 °C].
Remedy:
- check whether the fan is running.
- check the fan elements
- check whether the ambient temperature is in the permissible range.
Notice:
This fault can only be acknowledged after this alarm threshold for alarm A05002 has been undershot.
230036
<location>Power unit: Electronics board overtemperature
Message
%1
value:
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The temperature in the module slot of the drive converter has exceeded the permissible temperature
limit.
- insufficient cooling, fan failure.
- overload.
- ambient temperature too high.
Fault value (r0949, interpret decimal):
Temperature [1 bit = 0.1 °C].
© Siemens AG 2009 All Rights Reserved
SINUMERIK 840D sl, 840Di sl, SINAMICS, Diagnostics Manual (DAsl), 03/2009
Overview of Alarms
SINAMICS-Alarms
2-835