Overview of Alarms
SINAMICS-Alarms
207908
<location>Internal armature short-circuit active
Message
-
value:
Drive object:
SERVO, VECTOR
Reaction:
NONE
Acknowledge:
NONE
Cause:
The Motor Module signals that the motor is short-circuited through the power semiconductors (r1239.5
= 1). The pulses cannot be enabled. The internal armature short-circuit is selected (p1231 = 4):
Remedy:
For synchronous motors, the armature short-circuit braking is activated if a 1 signal is present via
binector input p1230.
See also: p1230 (Armature short-circuit / DC brake activation), p1231 (Armature short-circuit / DC
brake configuration)
207909
<location>Internal voltage protection: De-activation only effective after
POWER ON
Message
-
value:
Drive object:
SERVO, VECTOR
Reaction:
NONE
Acknowledge:
POWER ON
Cause:
The de-activation of the internal voltage protection (p1231 not equal to 3) only becomes effective after
POWER ON.
The status signal r1239.6 = 1 indicates that the internal voltage protection is ready.
Remedy:
None necessary.
This a note for the user.
207910
<location>Drive: Motor overtemperature
Message
%1
value:
Drive object:
SERVO, VECTOR
Reaction:
NONE
Acknowledge:
NONE
Cause:
KTY:
The motor temperature has exceeded the fault threshold (p0604 or p0616).
VECTOR: The response parameterized in p0610 becomes active.
PTC:
The response threshold of 1650 Ohm was exceeded.
Alarm value (r2124, interpret decimal):
SME not selected in p0601:
1: No output current reduction.
2: Output current reduction active.
SME selected in p0601 (p0601 = 10):
The number specifies the sensor channel that resulted in the alarm being output.
See also: p0604 (Motor overtemperature alarm threshold), p0610 (Motor overtemperature response)
Remedy:
- check the motor load.
- check the motor ambient temperature.
- check KTY84.
207913
<location>Excitation current outside the tolerance range
Message
-
value:
Drive object:
SERVO, VECTOR
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The difference between the excitation current actual value and setpoint has exceeded the tolerance:
abs(r1641 - r1626) > p3201 + p3202
The cause of this fault is again reset for abs(r1641 - r1626) < p3201.