Honeywell GSMX Installation And Setup Manual page 19

Gsm communicator
Table of Contents

Advertisement

GSMX Installation and Setup Guide
PROMPTS
ENTRY
18
Supervi-
sion
(24
Hours)_
19
Old Alarm
Time
(10
Minutes)_
20
GSM Flt
Time
(00 mins)_
OPTIONS
• 30 Day
The AlarmNet network must hear
at least one supervisory message
• 24 Hour
from the module during this
• None
supervision period; otherwise,
AlarmNet notifies the central
station that a communication
failure has occurred. (If the
supervision period is changed
after registration, you must re-
register the module.)
Press the [space] key to scroll
through choices.
UL NOTE: Must be 24 hour.
• 10
The old alarm time sets how long
an undeliverable alarm is retried
Minutes
for delivery to the central station.
• 15
If the message is not validated, it
Minutes
is retried until the old alarm time
• 30
is reached or the message is
Minutes
validated.
• 1 Hour
Press the [space] key to scroll
• 2 Hours
through choices.
• 4 Hours
UL NOTE: Must be 10 minutes.
• 8 Hours
• 12 Hours
• 24 Hours
[01-99]
In the event the module detects a
communication path failure,
[00] = not
enter the time delay (in minutes)
used
before the module notifies the
control panel with a trouble
message. The control panel can
then notify the central station.
UL NOTE: Must be one (01)
minute.
– 17 –