Honeywell Excel 10 W7752D User Manual page 64

Fan coil unit controllers lns plug-ins
Table of Contents

Advertisement

EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE
NV name
field name
nvoStatus
object_id
nvoStatus
invalid_id
nvoStatus
invalid_request
nvoStatus
disabled
nvoStatus
comm_failure
nvoStatus
in_alarm
nvoStatus
report_mask
nvoTerminalLoad
nvoUnitStatus
mode
EN2B-0285GE51 R0909
Table C4. Output Variables for Excel 10 FCU Controllers.
digital
engineering units:
state
English (metric) or states plus
or
range
value
UWORD
NODE_OBJECT
0
FCU_OBJECT
1
Bit
VALID_ID
0
INVALID_ID
1
Bit
VALID_REQUEST
0
INVALID_REQUEST
1
Bit
ENABLED
0
DISABLED
1
Bit
COMMUNICATION_OK
0
COMMUNICATION_FAILURE
1
Bit
NO_ALARM
0
IN_ALARM
1
Bit
NO_REPORT_MASK
0
REPORT_MASK
1
SNVT_lev_percent
-163..163%
163.835% = INVALID
SNVT_hvac_mode
HVAC_HEAT
1
HVAC_COOL
3
HVAC_OFF
6
default
nviSpaceTemp is bound to another node, nvoSpaceTemp is not
reported on the network.
This output variable belongs to the Node Object and reports the
status for any object on a node. This is the answer to the
nviRequest.
This output variable indicates whether nviRequest uses a fault
object ID.
This output variable indicates whether nviRequest uses a fault
request.
This output variable indicates whether the device is enabled or
disabled (nviManualMode = DISABLE).
This output variable indicates whether an update nviRcvHrtBt is
missing.
This output variable indicates whether an alarm occured. See
nvoAlarm.
This output variable shows the answer to nviRequest >
REPORT_MASK
This output variable shows the terminal load, which is a percentage
between -160% and +160% based upon the control output level.
Negative values indicate heating load and positive values indicate
cooling load. 100% is the full terminal capacity. An absolute
terminal load value of more than 100% indicate that the terminal is
not able to supply the required heating or cooling energy which at
the zone controller should cause a demand for more supply
energy. nvoHeatOutput will be transmitted immediately when its
value has changed significantly (>= 1%).
This output variable reports the last operating mode of the control
algorithm. It is not set to HVAC_OFF if the Heating and Cooling
Output shows 0%. HVAC_OFF is set when the Device is disabled
from nviRequest, nviManualMode or nviApplicMode.
62