Overview
These instructions apply to the following kit: 51500324-501 Top Cover Assembly with Display Upgrade
Kit and its application to the 10260S Series Actuators. This kit allows you to add or replace the local
display/keypad control function to 10260S actuators.
Summary
The top cover assembly of the 10260S contains the display and keypad components which are the local
interface for actuator operation. The transformer is also mounted inside the top cover. The transformer uses
the input power to provide internal voltages to the power distribution and main PWA. See Figure 1. Follow
the procedure in Table 1 to install or replace the top cover assembly.
Tools Needed
To perform the installation procedure, you will need the following tools:
• Medium Flat-blade screwdriver
• Medium Phillips screwdriver
• Small needle-nosed pliers
Procedure
WARNING
Disconnect power before accessing components inside the actuator.
ATTENTION
When working with Printed Wiring Assemblies (PWAs) always protect against electrostatic discharge by
wearing a grounded wrist strap.
62-86-33-25
10260S Series Actuators
Page 1 of 5

Advertisement

loading

Summary of Contents for Honeywell 10260S Series

  • Page 1 Overview These instructions apply to the following kit: 51500324-501 Top Cover Assembly with Display Upgrade Kit and its application to the 10260S Series Actuators. This kit allows you to add or replace the local display/keypad control function to 10260S actuators.
  • Page 2 Top Cover Assembly Kit Instruction, continued Top Cover Assembly Transformer Extended Cover Assembly Terminal Panel Cover Figure 1 Top Cover Assembly Location Table 1 Top Cover Assembly Installation Procedure Step Action Remove AC power to the actuator. Remove the seven screws and separate the extended cover from the actuator case. See Figure 1.
  • Page 3 Top Cover Assembly Kit Instruction, continued Step Action Disconnect three wire connectors from the edge connectors (Phv, Pan and Pcpu) on the power distribution PWA. See Figure. Pcpu Ppwr Pmtr Power Distribution PWA Connectors for Transformer cables Disconnect wire connector from Ppwr connector on power distribution PWA. Remove black and gray wire leads at pins 5 and 6 of the connector.
  • Page 4 Top Cover Assembly Kit Instruction, continued Step Action If replacing the top cover assembly – Disconnect the wire connector from J4 of the power distribution PWA. See figure in step 4. Remove top cover assembly from actuator. Install the new top cover assembly by first connecting the wire connector to J4 on the power distribution PWA.
  • Page 5 Contact your local sales office for warranty information. If warranted goods are returned to Honeywell during the period of coverage, Honeywell will repair or replace without charge those items it finds defective. The foregoing is Buyer’s sole remedy and is in lieu of all other warranties, expressed or implied, including those of merchantability and fitness for a particular purpose.