Honeywell Excel 10 W7752D User Manual page 53

Fan coil unit controllers lns plug-ins
Table of Contents

Advertisement

NV name
field name
nviTest
fan_control
nviTest
override_LED
nviTodEvent
current_state
nviTodEvent
next_state
nviTodEvent
time_to_next_state
Table C3. Input Variables for Excel 10 FCU Controllers
digital
engineering units:
state
English (metric) or states plus
or
range
value
BYTE
NORMAL_FAN_MODE
0
OFF1_OFF2_OFF3
1
ON1_OFF2_OFF3
2
OFF1_ON2_OFF3
3
ON1_ON2_OFF3
4
OFF1_OFF2_ON3
5
ON1_OFF2_ON3
6
OFF1_ON2_ON3
7
ON1_ON2_ON3
8
BYTE
NORMAL_LED_MODE
0
LED_OFF
1
LED_ON
2
SNVT_tod_event.current_state
OC_OCCUPIED
0
OC_UNOCCUPIED
1
OC_STANDBY
3
OC_NUL
255
SNVT_tod_event.next_state
OC_OCCUPIED
0
OC_UNOCCUPIED
1
OC_STANDBY
3
OC_NUL
255
SNVT_tod_event.time_to_next_s
tate
UWORD
0 to 2880 minutes
EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE
default
NORMAL_FAN_MODE
This input variable is used to test the fan speed relays.
(at application restart)
NORMAL_LED_MODE
This input variable can be used to test the wall module LED when
(at application restart)
nviManualMode = MODE_MANUAL.
OC_OCCUPIED
This input variable indicates to the node whether the space is
(if bound but fails to be
currently scheduled to be occupied, standby or unoccupied.
received or at application
restart)
OC_OCCUPIED
This input variable indicates to the node whether the next
(if bound but fails to be
scheduled occupancy mode will be occupied, standby or
received or at application
unoccupied. This information is required by the controller to
restart)
perform the optimum start strategy.
0 (if bound but fails to be
This input variable specifies the time in minutes until the next
received or at application
change of scheduled occupancy state. This data is also used by
restart)
the optimum start calculation (see nciEnergyManag).
51
comments
EN2B-0285GE51 R0909