Honeywell Excel 10 W7752D User Manual page 39

Fan coil unit controllers lns plug-ins
Table of Contents

Advertisement

NV name
field name
nciApplVer
application_type
nciApplVer
version_no
nciApplVer
time[0]
nciApplVer
time[1]
nciApplVer
time[2]
nciApplVer
time[3]
nciDeviceName
ch[0-17]
nciLocation
nciMaxSendTime
Table C2. Configuration Variables for Excel 10 FCU Controllers
digital
engineering units:
state
English (metric) or states
or
plus range
value
UBYTE, 0 to 255
UBYTE, 0 to 255
UBYTE, 0 to 255
UBYTE, 0 to 255
UBYTE, 0 to 255
UBYTE, 0 to 255
UBYTE, 0 to 255
SNVT_str_asc
SNVT_temp_p
0 to 6553 seconds
EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE
default
0
This configuration variable specifies the current application number of
the Excel 10 application.
0
This configuration variable specifies the version number of the Excel
10 application.
0
The time stamp of the last change to the Excel 10 application con-
figuration. Time meets the ANSI C time stamp requirement specifying
the number of seconds elapsed since midnight (0:00:00), January 1,
1970. It is represented in the Intel Format and is four bytes in length.
0
See above.
0
See above.
0
See above.
0
This configuration variable specifies the name of each device. This is
an ASCII string with the a size of 18 characters. A name with all NULLs
means that the device has not been configured.
0x00
This configuration variable is used to provide more descriptive physical
loacation information than can be provided by the Neuron chip's 6 byte
location string.
0 s from factory
This configuration variable specifies the maximum time that expires
before the node object automatically transmits nvoStatus. This pro-
vides a heartbeat output that can be used by the destination objects to
ensure that the node is still healthy. The heartbeat output may be
disabled by setting nciMaxSendTime = 0.
37
comments
EN2B-0285GE51 R0909