Honeywell Excel 10 W7752D User Manual page 41

Fan coil unit controllers lns plug-ins
Table of Contents

Advertisement

NV name
field name
nciCntrlSettings
fan_run_up_time
nciCntrlSettings
fan_overrun_time
nciCntrlSettings
switch_level_cool[0]
nciCntrlSettings
switch_level_cool[1]
nciCntrlSettings
switch_level_cool[2]
nciCntrlSettings
switch_level_heat[0]
nciCntrlSettings
switch_level_heat[1]
nciCntrlSettings
switch_level_heat[2]
nciCntrlSettings
staging_hysteresis[0]
nciCntrlSettings
staging_hysteresis[1]
nciCntrlSettings
reheat_switch_level
Table C2. Configuration Variables for Excel 10 FCU Controllers
digital
engineering units:
state
English (metric) or states
or
plus range
value
SNVT_time_sec
0
0 to 600 seconds
SNVT_time_sec
0
0 to 600 seconds
SNVT_lev_percent
0 to 100%, 0 = Disable
SNVT_lev_percent
0 to 100%, 0 = Disable
SNVT_lev_percent
0 to 100%, 0 = Disable
SNVT_lev_percent
0 to 100%, 0 = Disable
SNVT_lev_percent
0 to 100%, 0 = Disable
SNVT_lev_percent
0 to 100%, 0 = Disable
SNVT_lev_percent
0 to 100%
SNVT_lev_percent
0 to 100%
SNVT_lev_percent
0 to 100%
EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE
default
0
This configuration variable specifies the time the fan runs before the
outputs are switched ON. It is typically used for electric heat outputs
with fan interlock (see nciFcuConfig.fan_interlock_0 and _1). The
interlock must be set.
0
This configuration variable specifies the time the fan still runs after the
control algorithm has turned OFF the cooling/heating outputs. It is
typically used for electric heat with fan interlock (see
nciFcuConfig.fan_interlock_0 and _1). The interlock must be set. In
case of smoke purge the overrun-time will be ignored.
5%
This is the switching level to turn ON stage 1 of the cooling equipment
(if configured as multistage).
50%
This is the switching level to turn ON stage 2 of the cooling equipment
(if configured as multistage).
75%
This is the switching level to turn ON stage 3 of the cooling equipment
(if configured as multistage).
5%
This is the switching level to turn ON stage 1 of the heating equipment
(if configured as multistage).
50%
This is the switching level to turn ON stage 2 of the heating equipment
(if configured as multistage).
75%
This is the switching level to turn ON stage 3 of the heating equipment
(if configured as multistage).
10%
This configuration variable applies only to cool outputs configured as
multistage outputs and specifies the hysteresis between switching the
cool stages ON and OFF.
10%
This configuration variable applies only to heat outputs configured as
multistage outputs and specifies the hysteresis between switching the
heat stages ON and OFF.
100%
This configuration variable specifies the switch-over control output level
for the reheat output.
39
comments
EN2B-0285GE51 R0909