EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE
NV name
field name
nvoFanSpeedSw
value
nvoFanSpeedSw
state
nvoFcuStatus
field_no
nvoFcuStatus
effect_occ
nvoFcuStatus
hw_override
EN2B-0285GE51 R0909
Table C4. Output Variables for Excel 10 FCU Controllers.
digital
engineering units:
state
English (metric) or states plus
or
range
value
NO_FAN
255
SNVT_switch.value
0 to 100%
SNVT_switch.state
OFF
ON
NO_FAN_SPEED_SW
UBYTE
FIELD_EFFECT_OCC
1
FIELD_HW_OVERRIDE
2
FIELD_SCHED_OCC
3
FIELD_EFF_SEN_OCC
4
FIELD_NET_MAN_OCC
5
FIELD_HW_SEN_OCC
6
FIELD_R_O_LED
7
FIELD_MODE
8
FIELD_ALARM_TYPE
9
FIELD_DLC_SHED
10
FIELD_EFF_WINDOW_OPEN
11
FIELD_HW_WINDOW_OPEN
12
FIELD_FAN_FEEDBACK
13
FIELD_EXTERNAL_ACTIVE
14
FIELD_FAN_STAGES_ACTIVE
15
FIELD_OUTPUT_POS_1
16
FIELD_OUTPUT_POS_2
17
FIELD_REHEAT_RELAY
18
FIELD_ACTIVE_SET_PT
19
20
FIELD_SPACE_TEMP
FIELD_REST_BYPASS_TIME
21
SNVT_occupancy
OC_OCCUPIED
0
OC_UNOCCUPIED
1
OC_BYPASS
2
OC_STANDBY
3
SNVT_occupancy
OC_UNOCCUPIED
1
OC_BYPASS
2
OC_NUL (No Override)
255
default
This output variable allows the fan speed switch of a master
controller to be used for all slave Excel 10 controllers in the same
room.
See above.
This output variable is used to indicate which other data field in
nvoFcuStatus has changed since the last time nvoFcuStatus was
sent out on the network. If any field has had a significant change,
only that field is updated, and field_no indicates which field. If three
or more fields have changed significantly, then all fields are
updated and field_no is set to 0. All fields are also updated every
refresh time (55s).
This output variable is the effective occupancy mode resulting from
scheduled occupancy mode, occupancy sensor information,
bypass push-button, or manual operator interface.
This output variable reports the current state of the remote override
button.
56