Special Zone Operation
A.5.3 How to View Presignal and PAS Selections
You can use the Read Status Entry option to view the current selection for the Presignal function.
To do so, press the keys in sequence:
NOTE: For instructions on programming the Presignal function, refer to the NFS2-640
Programming Manual.
The LCD display shows the current selections for the Presignal function. The figure below shows a
sample LCD display of a Presignal function selected for PAS and a Presignal Delay Timer of 60
seconds:
Status Off
Presignal Delay=60
Seconds
NOTE: If any monitor modules are programmed with a
occurs, zone F0 goes false and aborts the Presignal Delay Timer.
A.5.4 How to Respond to an Alarm with Presignal Delay Timer (no PAS)
If an alarm occurs with a Presignal Delay Timer (60-180 seconds), the control panel displays the
type of device and the SLC address of the device causing the alarm. If a second alarm occurs during
the Presignal Delay Timer, the control panel aborts the Presignal Delay Timer and activates all pro-
grammed outputs. A sample Alarm screen for a monitor module is shown below:
Status banner ALARM
A L A R M : M O N I T O R
First zone in the CBE list
(blank if no zone listed)
The
FIRE ALARM
until the alarm is corrected and you press the S
have the duration of the Presignal Delay Timer (60-180 seconds) to respond to the alarm before the
control panel automatically activates all outputs programmed to F0. You can take the following
actions:
To silence the panel sounder and change the
the
ACKNOWLEDGE
To abort the Presignal Delay Timer, press the
To manually activate all outputs programmed to F0, press the
Canadian applications). The Manual Evacuate screen appears, the panel sounder pulses and the
FIRE ALARM
screen display alternately at 3-second intervals.
If the Presignal Delay Timer reaches its programmed value, without operator intervention, the con-
trol panel activates all outputs programmed to F0.
64
O F F P R E S I G N A L F U N C T P R E S I G N A L D E L A Y
D E L A Y - 0 6 0
PAS selected
Figure A.8 Sample Read Status for Presignal Function
Type Code
MONITOR
M O D U L E A D D R 1 M 1 4 7
Z 0 0 4
Figure A.9 Sample Alarm Display Screen
LED flashes and the panel sounder pulses a steady tone. The control panel latches
/
key.
SCROLL DISPLAY
LED changes from flashing to steady. The Manual Evacuate screen and Alarm
Presignal and Positive Alarm Sequence (PAS) Operation
Presignal Function status banner
P A S = Y E S
F O O
Type Code and a fire alarm
PAS INHIBIT
1 0 : 1 4 A 0 4 1 5 1 5 1 M 1 4 7
R
key to reset the control panel. You
YSTEM
ESET
LED from flashing to steady, press
FIRE ALARM
key.
SYSTEM RESET
DRILL
NFS2-640 Operations P/N 52743:L4 06/10/19
Zone F00
SLC address of the
activated initiating device
key (Alarm Signal for