Read Status Operation
Silenceable A selection that specifies if the device can be silenced during an alarm by pressing
the
SIGNAL SILENCE
* = output nonsilenceable
F = silenceable, resound by fire alarm
U = silenceable, resound by supervisory alarm
B = silenceable, resound by security alarm
T = silenceable, resound by trouble
O = silenceable, does not resound
NOTE: If the "Strobe" Type ID is used with System Sensor Strobe synchronization, F,U, B, T,
or O will silence the entire circuit, "*" will silence the horn portion only.
Walk Test A selection that specifies if the device will activate during a Walk Test.
How to View Read Status for a Software Zone (Z01-Z99)
Software
Zone Number
next device
previous device
How to View Read Status for a Special Zone (F0-F9, FA-FC)
Special
Zone Number
next device
previous device
NOTE: The zone label depends on the type of Special Zone. For example,
CODE TYPE
Code Type selection
for Special Zone F8
NOTE: Special Function Zones FA, FB, and FC are represented in VeriFire Tools as ZF10,
ZF16, and ZF18, respectively.
46
key. Possible values are:
From the "Read Status" screen, press 0, then press the
key. You can now view Read Status for a Software Zone as fol-
lows: press Z, enter the zone number (01-99), then press the
ENTER
press Z, enter 07, then press the
now displays information for a Software Zone as shown below.
Zone status (ON or OFF)
Zone label for zones 01-99
O F F
S O F T W A R E Z O N E 3 R D F L O O R C A F E T E R I A
Figure 4.4 Sample Software Zone Read Status Display
From the "Read Status" screen, press 0, then press the
key. You can now view Read Status for a Special Zone as fol-
lows: press
press the
Zone F8: press
trol panel now displays information for a Special Zone as shown
below.
for F8.
Zone status (ON or OFF)
Zone label for Special Function F8
O F F C O D I N G F U N C T I O N C O D E T Y P E
M A R C H T I M E
Viewing and Printing a Read Status
key. For example, to read the status of Software Zone 07:
ENTER
Custom zone label for the zone
entered in during program Change
Zone Number
, enter the zone number (F0-F9, FA-FC), then
Z
key. For example, to read the status of Special
ENTER
, enter F8, then press the
Z
Indicates Special Zone F8
NFS2-640 Operations P/N 52743:L4 06/10/19
ENTER