Honeywell NOTIFIER NFS2-640 Operation Manual page 14

Fire alarm control panel
Hide thumbs Also See for NOTIFIER NFS2-640:
Table of Contents

Advertisement

Mass Notification Mode of Operation
Displays
the device, as shown below:
Status banner
Extended 12 character
custom label
Sends an MN Supervisory message to the LCD display, remote annunciators, History buffer,
installed printers, and CRT-2s.
Initiates any Control-By-Event actions
Activates special zone ZFE
Sends an MN Supervisory message to the proprietary receiver via the network, if applicable
3.4.4 How to Respond to an MN Supervisory
If the control panel indicates an MN supervisory, you can do the following:
1.
Press the
SUPERVISORY
annunciators, history buffer, installed printers, and CRTs. Pressing the
DISPLAY
2.
Correct the condition that activated the MN supervisory point.
3.
For a Latching event, press the system reset key to return the control panel to normal operation.
For a Non-latching event, the panel will return to normal operation once the supervisory
condition is corrected.
The control panel sends a "System Normal" message to the LCD display, History buffer and
installed printers, remote annunciators, and CRT-2s.
3.4.5 How the Control Panel Indicates a Mass Notification Trouble
When an initiating device activates, the control panel does the following:
Produces a pulsed audible tone
Activates any trouble relays and devices programmed as Trouble Pending, General Trouble or
General Pending
Flashes the panel's Trouble LED
Displays a Type Code that indicates the type of device that with a trouble
Displays
the device, as shown below:
Status banner
Extended 12 character
custom label
Sends an MN trouble message to the LCD display, remote annunciators, History buffer,
installed printers, and CRT-2s.
NFS2-640 Operations P/N 52743:L4 06/10/19
in the status banner on the LCD display, along with information specific to
MN SUP
Type Code of initiating device
M N S U P : E C S / M N S U P L
M A I N B L G
Z 0 0 4
Zone
Figure 3.6 Sample MN Supervisory Display
/
ACKNOWLEDGE
SCROLL DISPLAY
LED from flashing to steady. An Acknowledge message is sent to the remote
will acknowledge all MN supervisory events on the fire panel.
in the status banner on the LCD display, along with information specific to
MN TBL
Type Code of initiating device
M N T B L : E C S / M N T R O U B L E M O N S E C U R I T Y P O S T
M A I N B L G
S H O R T
Zone
Figure 3.7 Sample MN Trouble Display
S E C U R I T Y S T A T I O N
0 3 : 1 7 P 0 4 1 5 1 5 2 M 1 4 7
Time and date of trouble
key to silence the panel sounder and switch the
0 3 : 1 7 P 0 4 1 5 1 5 2 M 1 4 7
Time and date of trouble
Operation of the Control Panel
Custom descriptor for
this device location
Device address
/
ACKNOWLEDGE
SCROLL
Custom descriptor for
this device location
Device address
23

Advertisement

Table of Contents
loading

Table of Contents