Viewing and Printing a Read Status
See page 42 and 43 of the NFS2 640 Programming Manual.
See page 44 of the NFS2 640 Programming Manual.
See Page 42 of the NFS2 640 Programming Manual.
SEC_RLY and SUP_RLY (0= turn on by Fire Alarm, 1= turn on by Security, 2= turn on by
Supervisory).
BAT_SIZE (1= battery size is greater than 26 Ahr, 0= less than 26 Ahr).
C_DRILL (custom drill N= No custom drill, Y= Yes).
TERM_DATA (0= LCD80 Terminal using 7 bit data, 1= LCD80 Terminal using 8 bit data).
PRT_BAND (0= 2400, 1= 4800, 2= 9600).
NOTE: Please refer to the VeriFire Tools help file for information on programming the above
screen.
NFS2-640 Operations P/N 52743:L4 06/10/19
S5
R E G I O N = 0
L O C A L C O N T R O L = 1
Figure 4.10 System Function Selection 5 Screen
S6
F L A S H S C A N
L I D E T
Figure 4.11 System Function Selection 6 Screen
S7
N O D E : 0 0 0 . X X X , C L A S S X : N
T H R E S H O L D C H A N N E L A : H , C H A N N E L B : H
Figure 4.12 System Function Selection 7 Screen
S8
S E C _ R L Y : 1 S U P _ R L Y : 2 B A T _ S I Z E : 0 C _ D R I L L : N
T E R M _ D A T A : 0
Figure 4.13 System Function Selection 8 Screen
T B L . R E M I N D = 2
A L A . S C R O L L = Y
I P A C C E S S = 0
L I M O D
L 2 D E T
Y
Y
P R T _ B A U D : 2
C H A R G E R : Y
Read Status Operation
D C C - M O D E = N
L 2 M O D
Y
Y
49