Read Status Operation
Device Status The status of the detector: Normal, Alarm, or Test.
Type Code The software Type Code that identifies the type of detector. (Refer to "Point
Programming" in the NFS2-640 Programming Manual.)
Default CBE Zone Selection This is the first zone in the 5 zone CBE list. Defaults are Zone
001 (Heat detectors) Zone 002 (Ion detectors) Zone 003 (Photo detectors) Zone 004 (Laser
detectors) Zone 005 (Multisensor). Values may differ depending on point programming.
Current alarm reading (xxx%) The current alarm reading of the detector, as a percentage of
the alarm sensitivity setting.
Alarm sensitivity level (Ax) The alarm sensitivity (x=1-9) entered in the Detector Sensitivity
Screen.
Pre-Alarm sensitivity level The Pre-Alarm Sensitivity (1-9; 0 = Pre-Alarm not used) entered
in the Detector Settings Screen.
NOTE: Refer to "Detector Sensitivity Settings" in the NFS2-640 Programming Manual for more
information on the Pre-Alarm and Alarm Sensitivity settings
Cooperative Multi-Detector selection A smoke detector programmed to evaluate readings
from nearby detectors in making Alarm or Pre-Alarm decisions. Cooperative Multi-Detector
sensing also allows the combination of ionization with photoelectric technology in reaching an
alarm decision.
* – Multi-not used.
A – combines the detector's alarm decision with the next SLC address above.
B – combines the detector's alarm decision with the next SLC address below.
C – combines the detector's alarm decision with the next SLC address above and the next SLC
address below.
Alarm Verification (* or V)
* – Alarm Verification not programmed for this detector.
V – Alarm Verification enabled.
Alarm Verification is a user-defined global time function that can reduce the number of
nuisance alarms. Refer to page page 39 for more information.
Device SLC Address The SLC address of the detector.
How to View Read Status for a Control/Relay or Monitor Module
SLC address
next device
previous device
The display and descriptions of the fields are shown below:
Device status
Extended 12-
character
custom label
Figure 4.2 Sample Control/Relay or Monitor Module Read Status Display
44
Type Code (CONTROL)
O F F
C O N T R O L
D O O R H O L D E R # 2
Default CBE zone selection
Switch Inhibit: I selected, * not selected
Silenceable: O = selected, * = not selected (default)
From the "Read Status" screen, press 0, then press the
key. You can now view Read Status for a monitor or a con-
trol/relay module as follows: press
address, then press the
ENTER
tus of a FCM-1 module 2M147: press
147, then press the
key. The control panel now displays
ENTER
information about the module as shown in Figure 4.2.
I N T E N S I V E C A R E U N I T
Z 0 0 0
NFS2-640 Operations P/N 52743:L4 06/10/19
Viewing and Printing a Read Status
, enter the SLC
MODULE
key. For example, to read the sta-
, enter 2 then
MODULE
Label for the module
* O *
2 M 1 4 7
SLC Address (001-159)
M (module)
SLC number (1 or 2)
Walk Test selection:
W selected for Walk Test
* not selected
ENTER