Honeywell NOTIFIER NFS2-640 Operation Manual page 39

Fire alarm control panel
Hide thumbs Also See for NOTIFIER NFS2-640:
Table of Contents

Advertisement

Read Status Operation
How to Read Status for Annunciator Selections
To view the next three annunciator selection screens, press the
If UDACT=N, the control panel displays the Annunciator Selections 3 and 4 screen, addresses
A20-A32, as shown below:
48
Parameter
Description
LocT
One of three operating
modes of a PC or terminal
connected to the control
panel (through TB12 PC
Terminal)
BLINK=01
The rate at which all
intelligent control or all
monitor modules blink
during polling
ST=4
NFPA wiring style operation
for the SLC
ACS=N
Use ACS Selection Groups
Table 4.1 System Function Parameters (2 of 2)
Annunciator Selection screens specify the information that displays
on ACS annunciators. From the "Read Status" screen, press 0, then
press the
tions as follows: press Z, enter S, enter annunciation selection number
(1-4 for annunciator, 5-8 for other settings), press the
ple LCD displays for the Read Status of Annunciator Selection are
shown below:
A1=Address
S1
A N N U N S E L E C T I O N 1 :
A 5 = * A 6 = * A 7 = * A 8 = * A 9 = * A 1 0 = * A 1 1 = *
Figure 4.7 Annunciator Selection 1 Screen
S2
A N N U N S E L E C T I O N 2 :
A 1 5 = * A 1 6 = * A 1 7 = * A 1 8 = * U D A C T = N
Figure 4.8 Annunciator Selection 2 Screen
S3
A N N U N S E L E C T I O N 3 :
A 2 3 = * A 2 4 = * A 2 5 = * A 2 6 = * A 2 7 = * A 2 8 = *
S4
A N N U N S E L E C T I O N 4 :
A 3 2 = *
Figure 4.9 Annunciator Selections 3 and 4 Screens
LocT – terminal connected to control
panel and located in the same room
as the control panel.
LocM – terminal connected to control
panel but requires password for
operation.
RemT – terminal connected through a
modem for Read Status operations
only.
BLINK=00: No blink
BLINK=01: Devices blink on
BLINK=16: Devices blink every
4 – Class B SLC or
6 – both Class A and Class X SLC
N – No annunciator selected or
Y – Select and display ACS Selection
Groups
key. You can now view Read Status for System Func-
ENTER
ACS selection group
A 1 = H A 2 = * A 3 = * A 4 = *
A 1 2 = * A 1 3 = * A 1 4 = *
A 2 0 = * A 2 1 = * A 2 2 = *
A 2 9 = * A 3 0 = * A 3 1 = *
NFS2-640 Operations P/N 52743:L4 06/10/19
Viewing and Printing a Read Status
Settings
every poll.
16th poll.
key. Sam-
ENTER
(
) key.
NEXT SELECTION

Advertisement

Table of Contents
loading