Honeywell S7800A Installation Manual page 41

Keyboard display module
Hide thumbs Also See for S7800A:
Table of Contents

Advertisement

 
 
 
Table 21. 7800 SERlES String codes. (Continued)
 
String Code
215
VP HIGH DLY
216
VP HIGH TST
217
VP SETUP NEEDED
218
MAIN VALVE 1 OFF
219
MAIN VALVE 2 OFF
220
MAIN VALVE 1 ON
221
MAIN VALVE 2 ON
222
VPS OFF
223
VPS ON
 
7800 SERIES Fault Codes
Table 22 is a complete list of fault codes that may appear in the
fault code register. The Fault String Code register will contain
the corresponding String code identified in the table.
 
Table 22. 7800 SERlES Fault Codes.
 
 
Fault
Code
Fault Message (NOTE:
(Reg
FAULT n: is not in the Fault
40001)
and Strings Code)
0
Blank (no fault)
1
FAULT 1: NO PURGE CARD
2
FAULT 2: AC FREQUENY/NOISE
3
FAULT 3: AC LINE DROPOUT
4
FAULT 4: AC FREQUENCY
5
FAULT 5: LOW LINE VOLTAGE
6
FAULT 6: PURGE CARD ERROR
7
FAULT 7: FLAME AMPLIFIER
8
FAULT 8: FLAME AMP/SHUTR
9
FAULT 9: FLAME DETECTED
10
FAULT 10: PRE-IGNITION ILK
11
FAULT 11: RUNNING ILK ON
12
FAULT 12: LOCKOUT ILK ON
13
FAULT 13: AIRFLOW SW. ON
14
FAULT 14: HIGH FIRE SWITCH
15
FAULT 15: FLAME DETECTED
16
FAULT 16: FLAME-OUT TIMER
17
FAULT 17: MAIN FLAME FAIL
18
FAULT 18: FLAME DETECTED
19
FAULT 19: MAIN FLAME IGN.
20
FAULT 20: LOW FIRE SW OFF
21
FAULT 21: RUNNING ILK
22
FAULT 22: LOCKOUT ILK
23
FAULT 23: AIRFLOW SWITCH
24
FAULT 24: CALL SERVICE
25
FAULT 25: CALL SERVICE
26
FAULT 26: MAN-OPEN SW. OFF
27
FAULT 27: START SWITCH ON
28
FAULT 28: PILOT FLAME FAIL
 
String
Fault
String
Code
(Table 22)
0
73
8
9
7
60
88
34
33
35
85
100
53
12
40
35
37
64
35
65
57
99
54
13
24
24
70
107
76
41
7800 SERIES S7800A KEYBOARD DISPLAY MODULE
Table 22. 7800 SERlES Fault Codes. (Continued)
Fault
Code
Fault Message (NOTE:
(Reg
FAULT n: is not in the Fault
40001)
and Strings Code)
29
FAULT 29: LOCKOUT ILK
30
FAULT 30: RUNNING ILK
31
FAULT 31: LOW FIRE SW OFF
32
FAULT 32: AIRFLOW SWITCH
33
FAULT 33: PRE-IGNITION ILK
34
FAULT 34: CONTROL ON
35
FAULT 35: CALL SERVICE
36
FAULT 36: CALL SERVICE
37
FAULT 37: CALL SERVICE
38
FAULT 38: CALL SERVICE
39
FAULT 39: CALL SERVICE
40
FAULT 40: CALL SERVICE
41
FAULT 41: MAIN VALVE ON
42
FAULT 42: PILOT VALVE 1 ON
43
FAULT 43: IGNITION ON
44
FAULT 44: PILOT VALVE 2 ON
45
FAULT 45: LOW FIRE SW OFF
46
FAULT 46: FLAME AMP TYPE
47
FAULT 47: JUMPERS CHANGED
48
FAULT 48: DELAYED MV ON
49
FAULT 49: MAN-OPEN SW. ON
50
FAULT 50: JUMPERS WRONG
51
FAULT 51: FLAME TOO STRONG
52
FAULT 52: CALL SERVICE
53
FAULT 53: LOCKOUT SWITCH
54
FAULT 54: COMB. PRESSURE
55
FAULT 55: PURGE FAN SW ON
56
FAULT 56: BLOCK INTAKE
57
FAULT 57: PURGE FAN SW OFF
58
FAULT 58: COMB. PRESS/FLAME
59
FAULT 59: CALL SERVICE
60
FAULT 60: CALL SERVICE
61
FAULT 61: MV1 OFF
62
FAULT 62: MV2 OFF
63
FAULT 63: MV1 ON
64
FAULT 64: MV2 ON
65
FAULT 65: VPS OFF
66
FAULT 66: VPS ON
67
FAULT 67: AC PHASE
68
FAULT 68: PRE-IGNITION ILK
69
FAULT 69: CALL SERVICE
70
FAULT 70: CALL SERVICE
71-75
FAULT 71-75: DEVICE SPECIFIC
76-93
FAULT 76-93: ACCESSORY FAULT
94-127
FAULT 94-127: CALL SERVICE
Fault
String
Code
(Table 22)
54
101
57
13
85
27
24
24
24
24
24
24
69
80
47
81
57
32
50
28
71
51
36
24
55
26
91
20
90
26
24
24
218
219
220
221
222
223
10
85
24
24
29
11
24
65-0090-6

Advertisement

Table of Contents
loading

This manual is also suitable for:

7800 series

Table of Contents