7800 SERIES Sequence State Codes
Sequence state codes are provided by the Burner Control.
Each code is translated into two string codes for displaying an
associated message in two lines. Each code is also translated
into burner control state bits which may be used to generate
and control system diagrams on an operator interface. The
codes can also be retrieved from registers 40004, 40005, and
40013.
 
The Sequence State Codes shown in Table 20 are valid only if
the Fault Code has a value of zero. If the Fault Code is non-
zero, the sequence state field contains the sequence state
code when the lockout occurred.
 
 
 
Table 20. 7800 SERlES Sequence State Codes
and Associated register code values.
 
 
 
 
7800 SERlES
Register
Sequence
40003
State
Fault
LOCKOUT
code not
zero
0
UNUSED HISTORY 0
1
INITIATE
2
INITIATE HOLD: AC
FREQUENCY/
NOISE
3
INITIATE HOLD:
AC LINE DROPOUT
4
INITIATE HOLD:
AC FREQUENCY
5
INITIATE HOLD:
LOW LINE
VOLTAGE
6
STANDBY
7
STANDBY HOLD:
REM
REMOTE CONTROL
8
STANDBY HOLD:
START SWITCH
9
STANDBY HOLD: F/G
FLAME DETECTED
10
STANDBY HOLD:
T20
PRE-IGNITION
11
STANDBY HOLD: T7
RUNNING
INTERLOCK
12
STANDBY HOLD: T7
LOCKOUT
INTERLOCK
13
STANDBY HOLD:
AIRFLOW SWITCH
14
PURGE HOLD: T19
HIGH FIRE
SWITCH
15
PURGE DELAY:T19
HIGH FIRE
JUMPRD
 
 
String Code
Burner
 
Control
 
 
Line
Line
Uses
State
1
2
mm:ss
Bits
52
Table
8000h
 
16
0
0000h
 
48
0
0001h
49
8
4001h
 
49
9
4001h
 
49
7
4001h
 
49
60
4001h
 
103
0
0002h
 
104
94
4002h
 
104
106
4002h
 
104
35
4002h
 
104
86
4002h
 
104
101
4002h
 
104
54
4002h
 
104
13
4002h
 
93
40
4004h
 
89
39
4004h
 
7800 SERIES S7800A KEYBOARD DISPLAY MODULE
Table 20. 7800 SERlES Sequence State Codes
and Associated register code values. (Continued)
 
7800 SERlES
Register
Sequence
40003
State
16
PURGE HOLD:
TEST
RUN/TEST SWITCH
17
PURGE DELAY: T18
LOW FIRE JUMPRD
18
PURGE HOLD: F/G
FLAME DETECTED
19
PURGE
20
PURGE HOLD: T18
LOW FIRE SWITCH
21
PuRGE HOLD: T7
Running Interlock
22
PURGE HOLD:
LOCKOUT
INTERLOCK
23
PURGE HOLD:
AIRFLOW SWITCH
24
PURGE HOLD:
START SWITCH
25
PILOT IGN
26
PILOT HOLD: TEST
RUN/TEST
SWITCH
27
PILOT HOLD:
START SWITCH
28
MAIN IGN
29
MAIN IG HOLD:
MANUAL-OPEN
SWITCH
30
RUN
31
RUN PV HOLD:
LOW FIRE SWITCH
32
PVHOLD IGN
33
PV HOLD:
PV HOLD SWITCH
34
RUN/LOWFIRE:
TEST
RUN/TEST
SWITCH
35
POSTPURGE
36
STATE UNKNOWN 31
37
RESET/ALARM
TEST
38
SAFETY START
39
SAFETY1-1
40
SAFETY1-2
41
SAFETY1-3
42
SAFETY1-4
43
SAFETY1-5
44
Blank
45
PRE-IGNITION
37
String Code
Burner
 
Control
 
 
Line
Line
Uses
State
Bits
1
2
mm:ss
93
98
4004h
 
89
56
4004h
 
93
35
4004h
 
87
0
0004h
93
58
4004h
 
93
101
4004h
 
93
54
4004h
 
93
13
4004h
 
93
106
4004h
 
78
0
0008h
77
98
4008h
 
77
106
4008h
 
66
0
0010h
67
72
4010h
 
95
0
0020h
96
58
4020h
 
77
46
4008h
77
45
4008h
 
97
98
4020h
 
83
0
0040h
0
0000h
111
0
6000h
 
102
105
4002h
102
2
0008h
102
3
0008h
102
4
0008h
102
5
0008h
102
6
0008h
0
0
A000h
84
0
0008h
65-0090-6