Installation - Honeywell SMARTLINE RM77 Supplementary Instructions Manual

10 ghz radar (fmcw) level meter for distance, level, volume, flow, mass and reflection measurement of liquids
Table of Contents

Advertisement

INSTALLATION

SMARTLINE® RM77
3
WARNING!
If the device is to agree with the requirements for functional safety given in IEC 61508, you must
obey the installation instructions given in the handbook (document [N1]). The device must be
installed by approved personnel.
If the device is delivered with an antenna extension, antennas for stilling wells (DN80, DN100,
DN150 and DN200 Metallic Horn antennas) or the Wave Guide antenna, refer to the "Installation"
and "Operation" chapters in the handbook. Make sure that the values for menu items 2.3.5
STILLWELL D., 2.3.6 STILLWELL H. and 2.3.7 ANTENNA.EXT are correct.
Calibrate the device to make sure that the safety function operates correctly if:
• the device was delivered without an antenna, or
• the device is delivered with an antenna extension, antenna types for stilling wells (DN80,
DN100, DN150 and DN200 Metallic Horn antennas) or the Wave-Guide antenna
This maintenance task must be done and recorded by approved personnel. For more data, refer
to
Calibration procedure
on page 30.
For more data, refer to "Installation" in the handbook (document [N1]).
34-VF-25-105 iss.1 GLO April 15 US
www.honeywell.com/ps
11