7.5.2 Limits for supervisor menu functions related to device configuration

CAUTION!
2.6.1 HART ADDRESS is set to "0". If it is not set to "0", the safety function will not operate
correctly.
2.4.2 RANGE I is set to "4-20 / 3.6E" or "3.8-20.5 / 3.6E". If the error signal is set to "22 mA" or
"Hold", the safety function will not operate correctly.
2.5.4 MEASUR.MODE is set to "Direct". If the error signal is set to "TBF Partial" or "TBF Full",
the safety function will not operate correctly.
2.2.1 SET OUTPUT is not shown on the device display or in PACTware
shown, the output will change to the set test value, independent of the measured value. The
current output will go back to the measured value when the user makes the display or
PACTware
Menu
No.
2.3.1
2.4.1
34-VF-25-105 iss.1 GLO April 15 US
Function
Function description
ANTENNA.EXT
Optional antenna
extensions.These are
attached between the flange
and the antenna.
ANTENNA.TYP
Type of antenna. For more
data, refer to the "Technical
data" chapter in the
handbook.
DIST.PIECE
Optional distance piece
between the converter and
the process connection. This
is for high-temperature
applications more than
+150°C / +302°F. The distance
piece is 120 mm / 4.7¨ long.
For more data, refer to the
"Technical data" chapter in
the handbook.
go back to the menu level.
Function
Function description
TANK HEIGHT
The distance from the tank
connecting flange face /
thread stop down to the tank
bottom.
OUTPUT FUNC.
The output function. Select an
output function to scale the
current values in relation to a
given point (usually the device
process connection or the
tank bottom). The output
current value is shown on a
bar graph in normal mode if
the measurement name is the
same as the output function.
Conversion parameters are
shown if there is volume or
mass data in 2.8.1 INPUT
TABLE.
min:
0 mm / 0¨
max:
2000 mm / 78.7¨ or
2.3.1 TANK HEIGHT
PP Horn, PTFE Horn,
Metal. Horn, Wave
Stick, Wave Guide
min:
0 mm / 0¨
max:
2.3.1 TANK HEIGHT
min-max:
1...30 m /
3.3...98.4 ft
Distance, Level,
Distance
conversion, Level
conversion
www.honeywell.com/ps
OPERATION
Selection list
Default value
and comments
1
1
1
. If SET OUTPUT is
Selection list
Default value and
comments
Default value agrees
with the customer
order
Default value agrees
with the customer
order