OPERATION
7

7.5 User parameters

INFORMATION!
If you change a parameter in one or more of the menu items that follow, this will have an effect
on the safety function.

7.5.1 Limits for supervisor menu functions related to antenna configuration

WARNING!
If the device was delivered without an antenna, then calibrate the device to make sure that the
safety function operates correctly. For more data, refer to Calibration procedure on page 30
CAUTION!
This section gives data on the modification of a small number of parameters in the 2.0.0
SUPERVISOR menu. If it is necessary to change parameters in the 3.0.0 SERVICE menu or the
4.0.0 MASTER menu, contact your supplier.
If you change the values of one or more of the parameters given in the "User parameters"
section, this can have an unwanted effect on the safety function. Do a check of the safety function
after you change a parameter.
INFORMATION!
Safety function check
Safety function check
Safety function check
Safety function check
Make sure that the 4...20mA measurement range is correctly calibrated.
LEGAL NOTICE!
The manufacturer declines all responsibility for the correct operation of the safety function if
these parameters in the 3.0.0 SERVICE or 4.0.0 MASTER menus are changed by the customer.
Menu
No.
2.3.4
2.3.5
2.3.6
22
Function
Function description
STILLWELL EN.
If this menu item is set to
"YES", then you must give the
stilling well height and inner
diameter in menu items 2.3.5
STILLWELL D. and 2.3.6
STILLWELL H..
STILLWELL D.
The inner diameter of the
stilling well. If the device is
installed in a stilling well or
has a Wave-Guide antenna,
enter the diameter. The
device will use this data if you
set 2.3.4 STILLWELL EN. to
"YES". This menu item is not
shown if you set 2.3.4
STILLWELL EN. to "NO".
STILLWELL H.
The height of the stilling well.
If the device is installed in a
stilling well or has a Wave-
Guide antenna, enter the
height. The device will use
this data if you set 2.3.4
STILLWELL EN. to "YES". This
menu item is not shown if you
set 2.3.4 STILLWELL EN. to
"NO".
YES, NO
min-max:
22...999 mm / 0.9...39.3¨
min:
500 mm / 19.7¨
max:
2.3.1 TANK HEIGHT