Support For Sil-Approved Devices - Honeywell SMARTLINE RM77 Supplementary Instructions Manual

10 ghz radar (fmcw) level meter for distance, level, volume, flow, mass and reflection measurement of liquids
Table of Contents

Advertisement

TECHNICAL DATA
9
Electrical connections
Power supply
Input and output
Current output
Current output
Current output
Current output
Resolution
Error signal
Error tolerance
®
HART
HART
HART
HART
Description
Point-to-point operation
Multidrop operation
PROFIBUS PA
PROFIBUS PA
PROFIBUS PA
PROFIBUS PA
Description
FOUNDATION™ Fieldbus
FOUNDATION
Fieldbus
FOUNDATION
FOUNDATION
Fieldbus
Fieldbus
Description
Modbus
Modbus
Modbus
Modbus
Description
Other data
Other data
Other data
Other data
Response time (errors)
Diagnostic test frequency
Approvals and certification
SIL
1 HART® is a registered trademark of the HART Communication Foundation
2 When only one liquid is in the tank

9.5 Support for SIL-approved devices

If the manufacturer makes a modification that has an effect on the safety function of the device,
the manufacturer will tell you about the modification immediately.
38
Terminals output - Non-Ex / Ex i:
Terminals output - Non-Ex / Ex i:
Terminals output - Non-Ex / Ex i:
Terminals output - Non-Ex / Ex i:
12...30 VDC; min./max. value for an output of 22 mA at the terminal
Terminals output - Ex d:
Terminals output - Ex d:
Terminals output - Ex d:
Terminals output - Ex d:
16...36 VDC; min./max. value for an output of 22 mA at the terminal
±3 µA
Low: ≤ 3.6 mA acc. to NAMUR NE 43
High: ≥ 21 mA acc. to NAMUR NE 43
If an error is >2.5% of the output signal, this error has a "dangerous undetected
failure" status.
HART® protocol via passive current output
Yes. Current output = 4 mA. HART® Address = 0. Output current data that is
transmitted in less than 1 ms is ignored (this data filter agrees with HART® protocol
requirements).
Multidrop operation is not permitted because the current output (safety function)
must be set to 4 mA. Thus, the safety function cannot supply data about the device
status.
Not yet available. This option is not permitted.
Not yet available. This option is not permitted.
Not yet available. This option is not permitted.
Response time = value given in supervisor menu item 2.4.5 ERROR DELAY
If electrical power is not sufficient for correct operation of the device (worst
conditions for operation), the error is shown in less than 30 seconds.
1 time / day (firmware does an auto-diagnostic test)
SIL 2
2
Agrees with IEC 61508:2010 Parts 1 to 7
www.honeywell.com/ps
SMARTLINE® RM77
1
34-VF-25-105 iss.1 GLO April 15 US