Honeywell Notifier INSPIRE E10 Installation Instructions Manual page 64

Fire alarm control panels
Hide thumbs Also See for Notifier INSPIRE E10:
Table of Contents

Advertisement

Panel Installation
TECHNICAL DATA
24V Aux. Output
Voltage and Current 24 V ± 5%, max. 1 A
FARE Interface
Voltage and Current 24 V ± 5%, max. 0.17 A
Acknowledge Input
Monitoring
FRE Interface
FRE Relay:
FRE RETURN Input
Key Safe Interface
Drive output:
64
Min. Input high level voltage : ≥ 2.0 V
Max. Input low level voltage : ≤ 0.8 V
FARE Relay constant current for monitoring : 4 mA
(FARE Relay must not be activated at 4 mA)
Min detectable FARE Relay resistance : ≥ 120 Ω
Max detectable FARE Relay resistance : ≤ 1850 Ω
(Detailed Values for monitoring are software defined)
Max. CLOSED contact resistance : ≤ 100 mΩ
Min. OPEN insulation resistance : ≥ 1000 MΩ
Nominal switching capacity : 2 A / 60 V DC, 0.3 A / 42 V AC
Max. switching power : 60 W (DC), 37.5 VA (AC)
Max. switching voltage: 60 V DC, 42 V AC
Max. switching current: 2 A
Max. Input voltage (FAIL) : 24 V
Nominal voltage (NORMAL) : ≥ 10.8 V and ≤ 13.2 V
FAIL Input voltage : ≤ 10.8 V or ≥ 13.2 V
Min. Input voltage (FAIL) : 0 V
24 V ± 5%, 0.17A