Cables
EMC CONSIDERATIONS
PE
Good quality fire industry cable must be used incorporating drain
L
wires or screens. The drain wires or screens must be earthed
N
within the enclosure. Use cable manufacturers recommendations
for adequate earthing of the drain wires or screens along with the
procedures in this document.
Mains Protective Earth
Ensure the mains cable earth wire
colour green yellow, is
securely connected to the mains terminal block connection
marked Protective Earth 'PE'. Press the spring push button
and insert the wires
into the terminal block and release
the spring button. Check the wire is secured to the terminal.
The cable used for the primary supply must conform with the
electrical wiring specifications of the country and to local
requirements.
Cable screen or drain wire connection to Functional Earth
Ensure each drain wire or cable screen is adequately grounded
inside the enclosure each to a point on the Functional Earth bar.
Use the earth screw and clamp provided to achieve the required
earthing bond of each cable screen. Make sure the screws are
tightened and to gain low resistance contact for EMC purposes.
Use adjacent cable entry points for incoming cables.
Back box to Door Functional Earth
Ensure the earth cable on the left-centre side of the backbox is
secured to a spade connector on the door
.
14