CABLE TYPE AND ROUTING
Appropriate attention must be given to ensure the correct cable type is installed in accordance with 'as fitted
drawings', site specific information and recommendations of national standard and local regulations. The cables
must be installed using cable manufacturers recommended fixing and accessories.
To ensure product safety, only use cables that are tested against standards IEC 60332-1-2 and
IEC 60332-1-3 or IEC/TS 60695-11-21.
FIRE DETECTOR COVERS
Each fire detector may be supplied with a plastic dust cover. If supplied, the cover must be fitted to prevent dust
and dirt from the building work contaminating the fire detector.
EARTH CONTINUITY
All earth connection points must be clean to provide a good electrical conductivity path. To maintain the earth
continuity: all earth leads and fittings provided must be installed. The loop cable screen must be continued
through each system device on the loop circuit, whether the earth is connected to the device or not.
Do not use any part of building structure for earthing.
POWER SUPPLY
The power to the system is derived from the mains and battery supplies. Before making changes to the installed
equipment and associated wiring disconnect both mains and battery supplies to prevent inadvertent damage to
system equipment.
MAINS SUPPLY
Connect the panel to the AC mains power supply via a separate mains isolator or a suitably rated circuit breaker.
The rated voltage (e.g. 230 V AC) is specified on the panel type label. Mains supply to the panel must be via an
unswitched 5A fused spur unit. All mains powered equipment must earthed.
Notifier INSPIRE E10/E15 Control Panels - Installation instructions
23