Default Settings - Honeywell RAEGuard 3 User Manual

Fixed gas detector
Table of Contents

Advertisement

5 Default Settings

The following default configurations of RAEGuard 3 transmitter are as follows.
Function
Basic Password /
Advanced Password
Fault Current Output
Inhibit Current Output
Warning Current Output
Overrange Current Output
Sound and Visual Alarm
Location
Language
HART address
RS485 ID, Baud Rate
Fault Relay**
Low Alarm Relay*
High Alarm Relay*
Low Alarm Latch*
High Alarm Latch*
TWA/STEL
Calibration interval
* Alarm relays automatically reset when reading falls within thresholds. If relay configuraed to LATCHING,
then relays must be reset using the Magnetic Wand.
**Fault state (fault relay and analog output<1mA) is always non-latching.
The default configurations for sensor are as follows:
Default
Gas Name
Range
O
30.0%vol
2
H
S
100ppm
2
CO
500ppm
LEL
100%LEL
CH
-NDIR
100%LEL
4
For details of how to change the configuration of the RAEGuard 3 please refer to
section 12.
Value/setting
1111 / 8888
1 mA (±0.5 mA)
2 mA (±0.5 mA)
3 mA (±0.5 mA)
22 mA (±0.5 mA)
SP07J
A0000
English
0
1,19200
Energized
Energized
Energized
Non-Latching
Non-Latching
Disable
90
Low Alarm
Low Alarm
Type
19.5%vol
Falling
10ppm
Rising
25ppm
Rising
25%LEL
Rising
25%LEL
Rising
23
RAEGuard 3 User Manual
Selectable range
0000-7999,8000-9999
1 mA or 2 mA or 3 mA
1 mA or 2 mA or 3 mA
1 mA or 2 mA or 3 mA
21 mA or 22 mA or 23 mA
SP07J, SP07A
A000-Z9999
Chinese, English
0-63
1-247;
4800,9600,38400,57600
Energized, de-energized
Energized, de-energized
Energized, de-energized
Latching, non-latching
Latching, non-latching
Enable, disable
0-360 (day)
High Alarm
23.5%vol
20ppm
50ppm
50%LEL
50%LEL
High Alarm
Type
Rising
Rising
Rising
Rising
Rising