Appendix A - Modbus ® Protocol - Honeywell RAEGuard 3 User Manual

Fixed gas detector
Table of Contents

Advertisement

Appendix A - Modbus
RAEGuard 3 detectors support RS485 data transmission and communicate
as MODBUS RTU. The detector provides 4-byte register data.
Note: The communication only transmits the tested concentration value of
the gas.
For example: 34 hex = 52 decimal
RAEGuard 3 detector supports RS-485 ModBus communication function.
The following are the communication protocols that support this
communication.
Communication settings
Communication mode: RTU
Baud rate: 4800,9600,19200,38400,57600
Information structure / communication steps
RAEGuard 3 only supports the 0x03 (read-only register) function code, i.e.
The detector only supports reading values.
0x03: Read-only register
Request information:
Device
Function
Address
Code
Client ID
03
Response information:
Device
Function
Address
Code
Client ID
03
Note: The data sent by the detector is 4 bytes long.
For example:
Request:
Response:
Note: The maximum transmission distance of standard 1.5 mm
communication cable is less than 1 km.
®
Register
Register
Address
Address
High Byte
Low Byte
00
08
Byte
Count
Reading
04
Highest
Byte
01
03
00
01
03
04
81
RAEGuard 3 User Manual
Protocol:
Quantity of
Registers
High Byte
00
Register Value
Reading
Reading
Higher
High
Byte
Byte
08 00
02
45
00 00
00
D1
Quantity of
CRC
Registers
Low
Low Byte
Byte
02
CRC
CRC
Low
Byte
Reading
Low
CRC
Byte
C9
3A
6F
2
CRC
High
Byte
CRC
CRC
High
Byte
CRC