Honeywell RAEGuard 3 User Manual page 30

Fixed gas detector
Table of Contents

Advertisement

Clean air or high pure nitrogen
The RAEGuard 3 detector adopts a 2-point calibration method, i.e. zeroing
calibration and span calibration. The calibration of the detector should follow the
sequence below.
Note: The zero of the oxygen sensor does not need to be calibrated, nor does it
require bump test. Clean air in the environment (20.9% vol oxygen) can be used
to directly do span calibration.
Zero Calibration
Remove the Waterproof Cap and fit the RAEGuard 3 Calibration Cap.
1.
Put the magnet over the switch "√" for at least 3s.
2.
Click the left switch" ▲" to increment or decrement the values, use the right
3.
switch" ▼" to move to the next character. The basic password is: 1111, the
advanced password is: 8888, select the switch" √" for confirmation.
Select the switch" √" to enter the "Calibration & Test" menu as shown below.
4.
Gas type
O
2
H
S
2
CO
Flammable gas
Methane (NDIR)
RAEGuard 3 User Manual
Flow rate (L/min)
0.5 to 1.0
0.5 to 1.0
0.5 to 1.0
0.5 to 1.0
0.5 to 1.0
0.5 to 1.0
30