151430-L8
Note: Total worst case current draw on a single SBUS cannot exceed 1 amp. If a large number of accessory mod-
ules are required, and the worst case current draw will exceed the 2 amps total, then the current draw must
be distributed using RPS-1000 Power Expanders. Each RPS-1000 Power Expander provides an additional
SBUS, with an additional 1 amp of SBUS current. Wiring distance calculations are done separately for
each RPS-1000, and separately for each control panel SBUS.
RA-2000 Fire Annunciator
5815XL
5824 Serial/Parallel Printer Interface Module
5880 LED I/O Module
5865 LED Annunciator
RPS-1000 Intelligent Power Supply
5496 Intelligent Power Supply
ECS-50W
ECS-125W
ECS-VCM / ECS-VCM with ECS-SW24*
ECS-RCU2000 / ECS-RCU2000 with ECS-SW24* .210 amps /.325 amps
ECS-DUAL50W
ECS-DUAL50W WITH ECS-50WBU
Note: Refer to Table 3-2 if using SD SLC devices and Table 3-1 if using IDP SLC devices for maximum number
of each type of device that can be used per system.
* All devices must use the same SBUS and VBUS.
After calculating the total worst case current draw, refer toTable 4-1 for the maximum distance the modules can
be located from the panel on a single wire run. The table ensures 6.0 volts of line drop maximum. In general, the
wire length is limited by resistance, but for heavier wire gauges, capacitance is the limiting factor.
These cases are marked in the chart with an asterisk (*). Maximum length can never be more than 6,000 feet,
regardless of gauge used. The formula used to generate this chart is shown in the note below.
Table 4-1: Wire Distances Per Wire Gauge Using Copper Wire
Total Worst Case
Current Draw (amps)
0.100
1852 ft.
0.200
926 ft.
0.300
617 ft.
0.400
463 ft.
0.500
370 ft.
0.600
309 ft.
0.700
265 ft.
0.800
231 ft.
0.900
206 ft.
1.000 (Max)
185 ft.
Model Number
Wiring Distance: SBUS Modules to Panel
22 Gauge
18 Gauge
4688 ft.
2344 ft.
1563 ft.
1172 ft.
938 ft.
781 ft.
670 ft.
586 ft.
521 ft.
469 ft.
4-6
Control Panel Installation
Worst Case Current Draw
.120 amps
.150 amps
.040 amps
.250 amps
.200 amps
.010 amps
.010 amps
.010 amps
.010 amps
.115 amps /.185 amps
.010 amps
.010 amps
16 Gauge
* 6000 ft.
3731 ft.
2488 ft.
1866 ft.
1493 ft.
1244 ft.
1066 ft.
933 ft.
829 ft.
746 ft.
14 Gauge
* 6000 ft.
5906 ft.
3937 ft.
2953 ft.
2362 ft.
1969 ft.
1687 ft.
1476 ft.
1312 ft.
1181 ft.