Model IFP-2000/ECS Installation Manual
9.
Select one of the following options from the menu that displays.
1 - Review System
2 - Repeat JumpStart
3 - Accept Changes
4 - Discard Changes
8-3
Press 1 if you need to review the JumpStart configuration. The Review System menu
will appear. Press 1 to review Entire System or Press 2 for Changes Only.
Press 2 if you need to rerun JumpStart for any reason.
If you are ready to make the JumpStart configuration permanent, select 3.
The system will ask you if the installation contains any addressable duct detectors. If
there are none, select 2 for No and skip to Step 8. If the system contains duct
detectors, select 1 for Yes and continue with Step 3.
From the list that displays, select the SLC that contains the duct detectors.
The first photoelectric or ionization detector on the system will display. Select 1 for
DUCT and 2 for NonDUCT.
Press
to select the next detector. Select 1 for DUCT and 2 for NonDUCT.
Continue until all duct detectors have been selected. (Note: You can move backwards
through the list with
).
When you reach the last detector on this device, press
The system will ask you if there are more duct detectors in the system. If there are,
select 1 for Yes and repeat from Step 3. If there are no more duct detectors, select 2
for No and continue with Step 8.
The system will restart in 10 seconds. You can press 1 to restart
immediately.
After the system resets, it will use the new JumpStart configuration.
If you want to discard the changes, and keep the configuration you had before
running this JumpStart press 4.