ALL CALL
Key
Select
LED's
Select
Keys
LED
Color
Red
Select Keys
Green
ECS Control LED
Green
Red
ECS Message
LED
Green
Operation
Gain ECS Control at an LOC
Gain ECS Control as ECS Super User at an LOC
(only one ECS Super User is allowed ECS Control
in the system at a time).
Select all output group for microphone override
P/N LS10049-001SK-E Rev B
Ready
NON-ACTIVE CALL
Key
to Talk LED
Figure 1-1: ECS Front view
Table 1-1: LED Conditions
States
On
The corresponding area is active for the currently playing ECS message.
Off
The corresponding area is not active.
On
The corresponding area is active for the microphone.
Off
The corresponding area is not active for the microphone.
On
LOC has ECS Control and the user is able to make changes to the ECS.
Off
LOC does not have ECS Control.
On
The corresponding ECS event was activated by an ECS device.
Off
The corresponding ECS event was not activated from this LOC.
On
The corresponding ECS event is active and was generated from the LOC (or
was activated from another LOC, but this LOC now has ECS Control).
Table 1-2: ECS Control Request
Press the ECS Control Key and enter a code if prompted. If ECS
Control is available, the ECS Control LED will illuminate. If another
LOC has ECS Control, the display will be similar to the one shown.
Press 1 to request control. The LOC with ECS Control will then be able
to allow or deny the request.
From the idle screen, enter an ECS Super User access code and then
press the ECS Control Key. If ECS Control as Super User is available,
the ECS Control LED will illuminate. If another LOC has Super User
ECS Control, a request for Super User ECS Control will automatically
be made to the LOC with control. The LOC with Super User ECS
Control will then be able to allow or deny the request. (See Figure 1-2
for screen display example).
Key the microphone, wait for the Ready-to-Talk LED to light, press the
All Call Key, and then deliver your verbal message.
ECS Control
Key
ECS Control LED
Message (1-8)
Activate Keys
Message
LEDS
Meaning
Task
ECN: 13-0759