Honeywell Farenhyt IFP-2000 Manual page 174

Analog/ addressable fire system, emergency communication system
Table of Contents

Advertisement

151430-L8
Operation
Occurs When
Mode
A smoke
detector goes
into alarm or a
pull station is
activated.
Alarm
CO Detector
goes into Alarm
If more than 3
categories are
active at a single
time and ECS is
enabled, top
screen will
display, If ECS is
not enabled, it
will look like
bottom screen.
Table 10-2: Operations Mode Behavior
System Behavior
The dialer seizes control of the phone line and
calls the central station.
The on-board annunciator will sound loud,
steady beeps to distinguish Alarm signals. For
Fire Alarm, the sequence is a loud steady
beep.(Any notification devices attached to the
system will also sound). For ECS Alarm, the
sequence is four seconds on, one second off.
GENERAL ALARM LED is on.
The LCD displays a screen similar to this one.
Count of alarms. In this example,
are 5 in fire and 1 in ECS.
there
Press the down arrow to view the type
and location of alarm (Message
alternates with the date/time display).
Press the down arrow to view the alarm. A screen
similar to this one displays.
Press SILENCE to silence the annunciator (and any
notification devices attached to the system).
When the alarm condition clears, press RESET to
restore the panel to normal.
Note: Alarm and Prealarm are combined into
single alarm count
10-12
System Operation