If using the battery cable extenders provided (P/N 140643), mount the RBB or AB-55 cabinet no more
than 18" away from the main control panel cabinet. This will ensure that the battery cables reach the
battery terminals.
2.
Connect the main control panel battery cables to the battery cable extenders as shown in Figure 4-5.
Figure 4-5 Splicing Control panel Battery Cable to RBB or AB-55 Battery Cable Extenders
3.
Run extended battery cable from control panel cabinet through conduit to RBB or AB-55 cabinet. See Fig-
ure 4-6.
Conduit
Coupler
Conduit
Figure 4-6 Battery Connections in the RBB or AB-55 Cabinet
Cabinet
Mounting Holes
Figure 4-4 RBB or AB-55 Cabinet Mounting Holes
+
RBB / AB-55 Cabinet
Cover Screws
-
+
RBB / AB-55 Cabinet
Cover Screws
4-4
Control Panel Installation
-