Erasing An F-Key Macro; Using A Recorded F-Key Macro; F-Key Status Event; F-Key Map Inhibit - Honeywell Farenhyt IFP-2000 Manual

Analog/ addressable fire system, emergency communication system
Table of Contents

Advertisement

151430-L8
10.9.3

Erasing an F-Key Macro

1.
If an F-Key macro has already been recorded, you can erase it by accessing the F-Key Recording menu and
selecting the 'Erase FKEY Macro' option.
2.
The panel will return to the idle screen.
10.9.4

Using a Recorded F-Key Macro

1.
From the idle screen on any annunciator in the site, press the F-Key you want to activate.
2.
Once finished, to de-activate the macro press the F-Key again.
10.9.5

F-Key Status Event

When an F-Key is enabled, it activates its corresponding F-Key Active event. This is a status type event that can
activate outputs without showing any status on annunciator displays. This should be used for ancillary purposes
only.
10.9.6

F-Key Map Inhibit

The F-Keys have the ability to disable event - output group mapping for the purpose of simulating that the map
doesn't exist. This can be setup to allow for testing purposes where notification of an entire building is not
desired during the test. This option is programmable for each output group map through SKSS-2.
When an F-Key is active and a map in the system is set to be disable by Map Inhibit, the system will show a
trouble event indicating it as such.
10-20
System Operation

Advertisement

Table of Contents
loading

This manual is also suitable for:

Farenhyt ifp-2000ecsFarenhyt rps-2000