19
3.2.7 Configuration Parameter – 18 Bytes
Decimal
Byte
Bit
The selection Sensor Type
=00h:
=01h:
=02h:
=03h:
=04h:
=10h:
=11h:
=12h:
=13h:
=14h:
0
00-07
=20h:
=21h:
=22h:
=23h:
=30h:
=53h:
=80h:
=81h:
=82h:
=83h:
=Others: Reserved
Temperature Type
00
0: Celsius(°C), 1: Fahrenheit(°F)
01
Reserved
Data Resolution
02
0: 0.1℃, ℉ / Bit, 1: 1℃, ℉ / Bit
1
03
Reserved
Filter Type
04
0: Normal Filter, 1: Enhanced Filter
05-07
Reserved
2~3
-
CH0 Offset Value
4~5
-
CH1 Offset Value
6~7
-
CH2 Offset Value
8~9
-
CH3 Offset Value
10~11
-
CH4 Offset Value
12~13
-
CH5 Offset Value
14~15
-
CH6 Offset Value
16~17
-
CH7 Offset Value
Description
PT100,
0.00385,
PT200,
0.00385,
PT500,
0.00385,
PT1000,
0.00385,
PT50,
0.00385,
JPT100,
0.003916,
JPT200,
0.003916,
JPT500,
0.003916,
JPT1000,
0.003916,
JPT50,
0.003916,
NI100,
0.00618,
NI200,
0.00618,
NI500,
0.00618,
NI1000,
0.00618,
NI120,
0.00672,
NI1000LG, 0.00500,
Resistance Input,
Resistance Input,
Resistance Input,
Resistance Input,
-200~850°C, 0.1°C /count
-200~850°C, 0.1°C/count
-200~850°C, 0.1°C/count
-200~350°C, 0.1°C/count
-200~850°C, 0.1°C/count
-200~640°C, 0.1°C/count
-200~640°C, 0.1°C/count
-200~640°C, 0.1°C/count
-200~350°C, 0.1°C/count
-200~640°C, 0.1°C/count
-60~250°C,
0.1°C/count
-60~250°C,
0.1°C/count
-60~250°C,
0.1°C/count
-60~180°C,
0.1°C/count
-80~250°C,
0.1°C/count
-50~120°C,
0.1°C/count
1~2000Ω,
100mΩ /1count
10mΩ /1count
1~327Ω,
1~620Ω,
20mΩ /1count
1~1200Ω,
50mΩ/1count
HX-RIO3 Series
Default Value
0: PT100
0: Celsius(°C)
0
0
0
0: Normal Filter
0
0
0
0
0
0
0
0
0