8.2 Line Power Supply
Table 8.13. Line power supply.
Supply Terminals
Supply Voltage Nominal 208/230 V AC
Supply Voltage Nominal 460 V AC
Supply Voltage Nominal 600 V AC
AC line voltage low/line drop-out: During low AC line voltage or a line drop-out, the adjustable
frequency drive continues until the intermediate circuit voltage drops below the minimum stop level,
which corresponds typically to 15% below the adjustable frequency drive's lowest rated supply
voltage. Power-up and full torque cannot be expected at AC line voltage lower than 10% below the
adjustable frequency drive's lowest rated supply voltage.
Supply Frequency
Max. temporary imbalance between line phases
True Power Factor (λ)
Displacement power factor (cos φ)
Switching on input supply L1, L2, L3
Environment according to EN60664-1
The unit is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical
Amperes, 240/500/600/690 V maximum.
8.3 Motor Output and Motor Data
Table 8.14. Motor Output.
Motor Output Terminals
Output voltage
Output frequency
Switching on output
Ramp times
Table 8.15. Torque Characteristics Frame A, B, C.
Starting Torque
Starting Torque (Variable torque)
Overload Torque (Variable torque)
Starting torque (Constant torque)
Overload Torque (Constant torque)
Torque rise time in VCC
1) Percentage relates to the nominal torque.
2) The torque response time depends on application and load but as a general rule, the torque step
from 0 to reference is 4–5 x torque rise time.
31-00559-01
2
(independent of fsw)
L1, L2, L3
200 to 240 V AC ± 10%
380 to 280 V AC ± 10%
525 to 600 V AC ± 10% (Frame A, B, C) 525 to
690 V AC ± 10% (Frame D)
50/60 Hz ± 5%
3% of rated supply voltage
≥ 0.9 nominal at rated load
near unity (> 0.98)
Frame A, B, C: up to 10 HP maximum 2 times/
min, greater than 10 HP maximum 1 time/min
Frame D: maximum 1 time/2 min
Overvoltage category III/pollution degree 2
U, V, W
0-100% of supply voltage
0-590 Hz
Unlimited
1-3600 s
maximum 135% up to 0.5 s
maximum 110% for 60 s
maximum 110% for 60 s
maximum 110% for 60 s
maximum 110% for 60 s
10 ms
1
1
1
1
1
90