Table 8.4. Line Power Supply 3x200–240 V AC - Normal overload 110% for 1 minute,
75 to 125 HP.
Type Designation, HVFD3D...
Typical shaft output at 230 V [hp]
Typical shaft output at 230 V [kW]
Enclosure Size
IP21/NEMA 1
IP54/NEMA 12
Output Current
Continuous (3x230 V) [A]
Intermittent (3x230 V) [A]
Continuous kVA (230 V AC) [kVA]
Max. Input Current
Continuous (3x230 V) [A]
Additional Specifications
Estimated power loss at 230 V [W]
Max. cable cross-section
(line power, motor, brake and load sharing) [AWG/(mm
Efficiency
1) Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety
in voltage and cable conditions). These values are based on a typical motor efficiency (IE/IE3 border
line). Lower efficiency motors add to the power loss in the drive. Applies to dimensioning of drive cooling.
If the switching frequency is higher than the default setting, the power losses can increase. LCP and typ-
ical control card power consumptions are included. Options and customer load can add up to 30 W to
the losses, though usually a fully loaded control card and options for slots A and B each add only 4 W.
2) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency mea-
sured at nominal current. For energy efficiency class, see chapter Chapter 8.4 Ambient Conditions.
81
2
1, 2
2
)]
3A0750
3A1000
75
100
55
75
D1
D1
D1
D1
190
240
209
264
76
96
183
231
1505
2398
2x3/0
2x3/0
(2x95)
(2x95)
0.97
0.97
31-00559-01
3A1250
120
90
D2
D2
302
332
120
291
2623
2x3/0
(2x95)
0.97