Step 9.
Step 10. 3-02 Minimum Reference
Step 11. 3-03 Maximum Reference
Step 12. 3-41 Ramp 1 Ramp Up Time
Step 13. 3-42 Ramp 1 Ramp Down Time
Step 14. 3-13 Reference Site. Linked to Hand/Auto Local Remote.
5.4.3 Asynchronous Motor Set-up
Enter the motor data in parameter 1-20 Motor Power [kW] or 1-21 Motor Power
[HP] to 1-25 Motor Nominal Speed. The information can be found on the motor
nameplate.
Step 1.
Step 2.
Step 3.
Step 4.
Step 5.
5.4.4 Permanent Magnet Motor Set-up
Note: Only use permanent magnet (PM) motor with fans and pumps.
Initial Programming Steps
Step 1.
Step 2.
Programming motor data
After selecting PM motor in 1-10 Motor Construction, the PM motor-related
parameters in parameter groups 1-2* Motor Data, 1-3* Addl. Motor Data and 1-4*
are active.
The necessary data can be found on the motor nameplate and in the motor data
sheet.
Program the following parameters in the listed order
Step 1.
Step 2.
Step 3.
Step 4.
Step 5.
31-00559-01
If a jumper wire is in place between control terminals 12 and 27, set 5-12
Terminal 27 Digital Input to External Interlock. Otherwise, leave 5-12
Terminal 27 Digital Input at factory default No Operation.
1-20 Motor Power [kW] or 1-21 Motor Power [HP]
1-22 Motor Voltage
1-23 Motor Frequency
1-24 Motor Current
1-25 Motor Nominal Speed
Activate PM motor operation 1-10 Motor Construction, select (1) PM,
non-salient SPM.
Set 0-02 Motor Speed Unit to [0] RPM.
1-24 Motor Current
1-26 Motor Cont. Rated Torque
1-25 Motor Nominal Speed
1-39 Motor Poles
1-30 Stator Resistance (Rs)
Enter line to common stator winding resistance (Rs). If only line-line data
43