Table 8.7. Line Power Supply 3x380–480 V AC - Normal overload 110% for 1 minute,
50 to 125 HP.
Type Designation, HVFD3D3...
Typical Shaft Output [HP] at 460 V
Typical Shaft Output [kW]
Output Current
IP21/NEMA 1
IP55/NEMA 12
Output Current
Continuous (3x380–439 V) [A]
Intermittent (3x380–439 V) [A]
Continuous (3x440–480 V) [A]
Intermittent (3x440–480 V) [A]
Continuous kVA (400 V AC) [kVA]
Continuous kVA (460 V AC) [kVA]
Max. Input Current
Continuous (3x380–439 V) [A]
Intermittent (3x380–439 V) [A]
Continuous (3x440–480 V) [A]
Intermittent (3x440–480 V) [A]
Additional Specifications
Estimated power loss at rated max.
load [W]
IP21, IP55 max. cable cross-section
(line power, motor) [AWG/(mm
IP21, IP55 max. cable cross-section
(brake, load sharing) [AWG/(mm
Efficiency
1) Efficiency measured at nominal current. For energy efficiency class see Chapter 8.4 Ambient
Conditions.
2) Applies for dimensioning of frequency converter cooling. If the switching frequency is higher than the
default setting, the power losses may increase. LCP and typical control card power consumptions are in-
cluded.
31-00559-01
2
2
)]
1
3C0500
3C0600
50
60
37
45
C1
C1
C1
C1
73
90
80.3
99
65
80
71.5
88
50.6
62.4
51.8
63.7
66
82
72.6
90.2
59
73
64.9
80.3
739
843
1/0 (50)
1/0 (50)
2
)]
0.98
0.98
3C0750
3C1000
75
100
55
75
C1
C2
C1
C2
106
147
117
162
105
130
116
143
73.4
102
83.7
104
96
133
106
146
95
118
105
130
1083
1384
4/0 (95)
4/0 (95)
0.98
0.98
3C1250
125
90
C2
C2
177
195
160
176
123
128
161
177
145
160
1474
0.99
84