Recommended initialization procedure, via 14-22 Operation Mode
Step 1.
Step 2.
Step 3.
Step 4.
Step 5.
Default parameter settings are restored during start-up. This may take slightly lon-
ger than normal.
Step 6.
Step 7.
Manual initialization procedure
Step 1.
Step 2.
Factory default parameter settings are restored during start-up. This may take
slightly longer than normal. Manual initialization does not reset the following
adjustable frequency drive information:

5.4 Basic Programming

5.4.1 Commissioning with SmartStart
The SmartStart wizard enables fast configuration of basic motor and application
parameters.
Note: Motor data are required for the SmartStart set-up. The required data are normally
available on the motor nameplate.
31-00559-01
Press [Main Menu] twice to access parameters.
Scroll to 14-22 Operation Mode and press [OK].
Scroll to Initialization and press [OK].
Remove power to the unit and wait for the display to turn off.
Apply power to the unit.
Alarm 80 is displayed.
Press [Reset] to return to operation mode.
Remove power to the unit and wait for the display to turn off.
Press and hold [Status], [Main Menu], and [OK] at the same time while
applying power to the unit (approximately 5 s or until audible click and
fan starts).
15-00 Operating hours
15-03 Power Up's
15-04 Over Temp's
15-05 Over Volt's
At first power-up or after initialization of the adjustable frequency drive,
SmartStart starts automatically.
Follow on-screen instructions to complete commissioning of the adjustable
frequency drive. Always reactivate SmartStart by selecting Quick Menu Q4 -
SmartStart.
For commissioning without use of the SmartStart wizard, refer to Chapter 5.4.2
Commissioning via [Main Menu] or the Programming Guide.
41