String Code
String
160
Terminal T8 = 0
161
Terminal T8 = 1
162
Terminal T9 = 0
163
Terminal T9 = 1
164
Terminal T10 = 0
165
Terminal T10 = 1
166
Terminal T16 = 0
167
Terminal T16 = 1
168
Terminal T17 = 0
169
Terminal T17 = 1
170
Terminal T18 = 0
171
Terminal T18 = 1
172
Terminal T19 = 0
173
Terminal T19 = 1
174
Terminal T20 = 0
175
Terminal T20 = 1
176
Terminal T21 = 0
177
Terminal T21 = 1
178
Jumper 1 Intact
179
Jumper 1 Clipped
180
Jumper 2 Intact
181
Jumper 2 Clipped
182
Jumper 3 Intact
183
Jumper 3 Clipped)
The values that follow are generated when the
fault code is zero and the Expanded Annunciator
code indicates that one or more switches are
open. The Line 2 string code will indicate which
switch is open.
184
STANDBY HOLD (EA)
185
PURGE HOLD (EA)
186
PILOT HOLD (EA)
187
MAIN IG HOLD (EA)
188
RUN HOLD (EA)
189
POSTPURGE HOLD (EA)
190
PRE-IGNITION HOLD (EA)
191
-SKIPPED-
192
DEMAND T6 = 0
193
DEMAND T6 = 1
194
PILOT VALVE T8 = 0
195
PILOT VALVE T8 = 1
196
INTERMIT PV T8 = 0
197
INTERMIT PV T8 = 1
198
MAIN VALVE1 T9 = 0
199
MAIN VALVE1 T9 = 1
200
VP SWITCH T16 = 0
7800 SERIESS7800A2142 4-Line LCD Keyboard Display Module
String Code
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
Table 21. Table 21. 7800 SERIES String codes.
7800 SERIES Fault Codes
Table 22 is a complete list of fault codes
that may appear in the fault code register.
The Fault String Code register will contain
the corresponding String code identified in
the table.
Fault
Code
(Reg
40001)
0
1
2
3
4
5
6
7
8
9
10
11
12
61
String
VP SWITCH T16 = 1
MAIN VALVE2 T17 = 0
MAIN VALVE2 T17 = 1
INTRUPTD PV T21 = 0
INTRUPTD PV T21 = 1
DELAYED MV T21 = 0
DELAYED MV T21 = 1
START SW T21 = 0
START SW T21 = 1
VP START
VP MV2 ON
VP LOW DLY
VP LOW TST
VP MV1 ON
VP HIGH DLY
VP HIGH TST
VP SETUP NEEDED
MAIN VALVE 1 OFF
MAIN VALVE 2 OFF
MAIN VALVE 1 ON
MAIN VALVE 2 ON
VPS OFF
VPS ON
Fault Message
(NOTE: FAULT n: is not in
the Fault and Strings Code)
Blank (no fault)
FAULT 1: NO PURGE CARD
FAULT 2: AC FREQUENY/NOISE
FAULT 3: AC LINE DROPOUT
FAULT 4: AC FREQUENCY
FAULT 5: LOW LINE VOLTAGE
FAULT 6: PURGE CARD ERROR
FAULT 7: FLAME AMPLIFIER
FAULT 8: FLAME AMP/SHUTR
FAULT 9: FLAME DETECTED
FAULT 10: PRE-IGNITION ILK
FAULT 11: RUNNING ILK ON
FAULT 12: LOCKOUT ILK ON
Fault
String
Code
(Table
21)
0
73
8
9
7
60
88
34
33
35
85
100
53