To view and confirm Postpurge timing refer to the Commissioning page (see Fig. 65)
or in the BC Diagnostics page (see Fig. 78) for locations in the menu system. The
Commissioning page can only be viewed when the Burner Control is in an appropriate
state to permit commissioning. If it is in that state, current commissioning settings can be
viewed without actually starting the commissioning process.
Fig. 72. Confirm valve proving when option
The right and left arrow buttons are used to tab between the "Yes" and "No" commands.
When the decision is made the OK button is pressed to inform the burner control module.
A "No" command stops the commissioning and control returns back to the commissioning
menu. A "Yes" command causes the setting to be approved and one of the following pages
to automatically display next (directed by the burner control module):
• Valve Proving (VP) time confirmation (VP when setting is not disabled) – see next figure
• Postpurge time confirmation (VP when setting is disabled and postpurge time has been
configured) – see Fig. 74
• Burner commission reset (VP when setting is disabled and postpurge time was not
configured) – see Fig. 75
The user is asked to confirm the valve proving time setting in the following page (see next
figure). The time setting is displayed on the page, and the user confirms it with a "Yes"
answer or declines it with a "No" answer.
Fig. 73. Confirm valve proving time
The right and left arrow buttons are used to tab between the "Yes" and "No" commands.
When the decision is made the OK button is pressed to inform the burner control module.
A "No" command stops the commissioning and control returns back to the commissioning
menu. A "Yes" command causes the setting to be approved and one of the following pages
to automatically display next (directed by the burner control module):
• Postpurge time confirmation (postpurge time was configured earlier) – see next figure
• Burner commission reset (postpurge time was not configured earlier) – see Fig. 75
The user is asked to confirm the postpurge time setting in the following page (see next
figure). The time setting is displayed on the page, and the user confirms it with a "Yes"
answer or declines it with a "No" answer.
Fig. 74. Confirm postpurge time
The right and left arrow buttons are used to tab between the "Yes" and "No" commands.
When the decision is made the OK button is pressed to inform the burner control module.
A "No" command stops the commissioning and control returns back to the commissioning
menu. A "Yes" command causes the setting to be approved and the Burner commission
reset page (see next figure) to automatically be displayed (directed by the burner control
module).
7800 SERIESS7800A2142 4-Line LCD Keyboard Display Module