Device Address and Baud Rate
Assign each device in the system a unique address by setting the MODBUS ADDRESS (see
page 21). Only RTU communications with 1 Start Bit, 8 Data Bits, 1 Stop Bit and no, odd, or
even parity is supported.
NOTE: Assign a device address number from 01 to 255. 00 is not an acceptable address
number and will not work.
NOTE: In Table 16: Line 1 and Line 2 refer to the two lines of text on the S7800 Keyboard
Display Module. In Table 20: The String Code column references Table 21, String
Codes. In Table 16: The Burner Control State Bits column references Table 19,
Burner Con- trol State Bits.
Reg-
Address
ister
(hex)
(dec)
0000
40001
0001
40002
0002
40003
0003
40004
0004
40005
0005
40006
0006
40007
0008
40009
000A
40011
000B
40012
000C
40013
000D
40014
000E
40015
0010-
40017-
0019
40026
001A-
40027-
0023
40036
0024-
40037-
002D
40046
002E-
40047-
0037
40056
0038-
40057-
0041
40066
0042-
40067-
004B
40076
004C
40077
004D
40078
004F
40080
0050
40081
0052
40083
7800 SERIESS7800A2142 4-Line LCD Keyboard Display Module
Parameter
Read/
Name
Write
Burner Control
R
(BC) Fault Code
BC Fault String
R
Code
BC Sequence
R
State
BC State String
R
Code (line 1)
BC State String
R
Code (line 2)
BC Sequence
R
time
BC Total cycles
R
BC Total hours
R
BC Flame 1 sig-
R
nal strength
BC Flame 2 sig-
R
nal strength
BC State Bits
R
S7830 First Out
R
Code
S7830 State Bits R
BC Fault history
R
record 1
BC Fault history
R
record 2
BC Fault history
R
record 3
BC Fault history
R
record 4
BC Fault history
R
record 5
BC Fault history
R
record 6
BC Flame Failure
R
Response Time
BC Manufactur-
R
ing code
BC Type Code
R
S7800M/BC
R
Software version
EA Software
R
version
For-
mat
See Table 22. Non-zero value = Lockout
U16
number.
U16
See Table 21. Lockout text.
U16
See Table 20 (valid only if Fault code = 0).
U16
See Table 21. Simulates Line 1 of S7800.
U16
See Table 21. Simulates Line 2 of S7800.
U16
0-4095 Seconds.
U32
Max value is 0xFFFFFFFF.
U32
Max value is 0xFFFFFFFF.
0 to 255 represents 0.0 to 25.5 volts. Not
U16
clipped to 5.0V like S7800.
U16
0 to 4095. N/A for 7800 SERIES.
U16
See Table 19.
U16
Not supported from S7800.
U32
Newest fault record. See Table 23.
Second newest fault record. See Table 23.
Third newest fault record. See Table 23.
Fourth newest fault record. See Table 23.
Fifth newest fault record. See Table 23.
Oldest fault record. See Table 23.
U16
Tenths of Seconds.
U32
U16
See Table 18.
U32
U32
Does not apply.
53