Honeywell 7800 Series Product Data page 56

4-line lcd keyboard display module
Hide thumbs Also See for 7800 Series:
Table of Contents

Advertisement

7800 SERIESS7800A2142 4-Line LCD Keyboard Display Module
Burner Control Type Codes
The burner control type code indicates the
exact model number of the burner control.
See Table 18.
CODE
DEVICE DESCRIPTION
0
(undefined)
100
RM7800E
101
RM7800G
102
RM7800L
103
RM7800M
104
RM7838A
105
RM7838B
106
RM7840E
107
RM7840G
108
RM7840L
109
RM7840M
110
RM7885A
111
RM7888A
112
RM7890A
113
RM7895A
114
RM7895B
115
RM7823A
116
RM7824A
117
RM7830A
118
RM8738C
119
RM7845A
120
RM7850A
121
RM7865A
122
RM7865B
123
RM7865C
124
RM7890B
125
RM7890C
126
RM7890D
127
RM7895C
128
RM7895D
129
RM7895E
130
RM7895F
131
RM7896A
132
RM7896B
133
RM7896C
134
RM7896D
135
RM7897A
136
RM7897C
137
RM7898A
138
R7140G
139
R7140L
140
R7140M
199
RM78xx
32-00110-07
CODE
DEVICE DESCRIPTION
200
EC7810A
201
EC7820A
202
EC7830A
203
EC7850A
204
EC7885A
205
EC7890A
206
EC7895A
207
EC7895C
208
EC7823A
209
EC7840L
210
EC7865
299
EC78xx
Table 18. Burner Control Type Codes.
7800 SERIES Burner Control State
Bits
The burner control sequence state is
translated into State Bit Register as shown
in Table 19.
BIT Description
0
Initiate
1
Standby
2
Purge
3
Pilot Ignition 0000 0000 0000 1000
4
Main Ignition 0000 0000 0001 0000
5
Run
6
Postpurge
7
Pre-Ignition
8
Valve Proving 0000 0001 0000 0000
13
Alarm
14
Hold
15
Lockout
Table 19. Burner Control State Bits.
7800 SERIES Sequence State
Codes
Sequence state codes are provided by the
Burner Control. Each code is translated
into two string codes for displaying an
associated message in two lines. Each code
is also translated into burner control state
bits which may be used to generate and
control system diagrams on an operator
interface. The codes can also be retrieved
from registers 40004, 40005, and 40013.
The Sequence State Codes shown in Table
20 are valid only if the Fault Code has a
56
BC State Bits Register
0000 0000 0000 0001
0000 0000 0000 0010
0000 0000 0000 0100
0000 0000 0010 0000
0000 0000 0100 0000
0000 0000 1000 0000
1010 0000 xxxx xxxx
NOTE: Lockout bit is also
set.
0100 0000 xxxx xxxx One
other bit may be on.
1010 0000 0000 0000
NOTE: Alarm bit is also set.

Hide quick links: