Honeywell 7800 Series Product Data page 45

4-line lcd keyboard display module
Hide thumbs Also See for 7800 Series:
Table of Contents

Advertisement

Fig. 68. Invalid commissioning login
If the login is unsuccessful, the user can retry the login by tabbing back to the password
digits using the left or right arrow buttons and re-edit the password.
After a successful login the next commissioning page is automatically displayed (directed
by the burner control module) to setup one of these parameters depending on the model:
• Valve Proving (VP) when option – see next figure
• Postpurge time – see Fig. 71
When valve proving is supported in the burner control module the feature is enabled by
specifying when it should occur:
• Not enabled (feature is disabled)
• Enabled prior to RUN (occurs prior to ignition trials)
• Enabled after RUN (after burner is running and before internal safety relay dropout
state)
• Enabled before and after RUN (occurs at both times prior to and after RUN)
• Enabled half before & after RUN (high pressure test occurs prior to RUN and low
pressure test occurs after RUN)
The setting is selected by scrolling these choices using the up and down arrow buttons (see
Fig. 69). The current parameter setting is displayed when the page is initially entered.
Fig. 69. Commission valve proving when option
The up and down arrow buttons are used to scroll through the choices on the edit line.
The right and left arrow buttons are used to tab to the save commands, "Yes" and "No".
When the input focus is on the save commands the up and down arrow buttons scroll
between "Yes" and "No". When the choice is set to the desired value the "Yes" command is
selected and the OK button is pressed to commit the change. If the user decides not to save
the choice and exit commissioning, the "No" command is selected and the OK button is
pressed.
When the setting is commissioned into the burner control module ("Yes" command is
selected) the next page displayed is one of the following (directed by the burner control
module):
• Valve Proving (VP) time commission (when VP is not disabled) – see next figure
• Postpurge time commission (when VP is disabled and postpurge time is supported in
BC) – see Fig. 71
• Valve Proving (VP) when confirmation (when VP is disabled and postpurge time is not
supported in BC) – see Fig. 72
When valve proving is enabled in the burner control module the time duration of the test is
configured (see Fig. 70).
NOTE: Tolerance on value proving timing value is +/- 10%.
The current setting is displayed allowing the user to change it to a new value. This time
parameter has a range of 0-63 minutes with times that must be set in the following
manner:
• 0-60 seconds in 1 second increments
• 1-10 minutes in 10 second increments
• 10-63 minutes in 1 minute increments
7800 SERIESS7800A2142 4-Line LCD Keyboard Display Module
45
32-00110-07