Connecting the Chassis to Ground

Attaching the Grounding Cable

Warning
Cisco 11500 Series Content Services Switch Hardware Installation Guide
2-24
The following procedure describes how to attach:
The grounding lug to the grounding cable
The grounding cable to the chassis
When you install or replace the unit, the ground connection must always be
made first and disconnected last.
1.
Power off the chassis by setting the power switch (or switches) to the O (off)
position.
2.
Strip the covering from the end of the grounding wire
amount of covering to be stripped varies depending on the type of lug you
plan to attach to the wire.
Lug
Panduit no. LCD6-10A-L
(supplied in accessory kit)
Panduit no. LCC6-10A-L
(long barrel)
Thomas & Betts no.
256-30695-1183(*4*)
Burndy no. YA6CL2TC10
3.
Insert the stripped end of the grounding wire into the open end of a lug
(Figure
2-10) and crimp the grounding lug securely to the wire. Use the lug
manufacturer's recommended crimping tool and crimping procedure to
ensure a proper crimp.
Strip Length
13/16 inch (2 cm)
1 1/16 inch (2.7 cm)
3/4 inch (1.9 cm)
7/8 inch (2.2 cm)
Chapter 2
Cabling the CSS
(Figure
2-10). The
78-13884-03